4.4.
Installation
ATTENTION: The partly-completed machine that is the object of this manual is part of a refrigeration
system consisting of the condensing unit and components of a refrigeration system such as
evaporator(s), pipes, safety components, etc.
The total volume of the evaporators associated with the partly-completed machine must NOT exceed
9 litres.
ATTENTION: During operations, the operator must wear all the necessary Personal Protective
Equipment (PPE).
DANGER: If the partly-completed machine is installed in closed environments, correct air
recirculation must be ensured and acoustic-visual detection and signalling systems must be
installed that intervene in the event of a refrigerant gas leak. Furthermore, for this type of installation,
the constraints imposed by the laws of the installation country must be complied with.
DANGER: The installation surface must permanently support the weight of the machine, persons and
equipment necessary for safe maintenance. Overloads should be considered in compliance with
the conditions of the installation site and respecting the restrictions imposed by the laws of the
country of installation.
DANGER: Perform the required interventions using appropriate work tools and paying the utmost
attention to elements that could cause accidents and in compliance with the legislation in force in
the country of installation.
DANGER: There must be no access to rooms at a lower level and/or to wells close to the installation
site of the partly-completed machine (this is to avoid any gas leak being channelled, such as
heavy gas).
DANGER: The R744 (CO2) refrigerant is colourless and odourless. Its presence in the environment
can cause asphyxiation. All operations must be carried out using gas presence detectors and in
compliance with the safety regulations of the country of installation.
Before proceeding with installation it is necessary to develop a refrigeration system housing project in which
the following are defined:
x
all components of the refrigeration system (e.g. condensing unit, evaporator, pipes, safety
components, etc.);
x
all the power, command and communication power lines;
x
location of the system;
x
piping route (lay-out).
The partly-completed machine must be installed on a horizontal plane to enable carrying out of the
necessary maintenance safely. The following figure shows the minimum distances regarding the
recommended safety distances. Secure the machine to the floor by using the holes on the anti-vibration
supports.