4.4.1.Oil fill
The oil must be added according to the refrigerant load as indicated in the table. If the
refrigerant load is LOWER than 4kg, no oil must be added.
REFRIGERANT LOAD
R744
UP TO 4kg
OVER 4kg
OIL
LOAD
PAG100
DO NOT
ADD OIL
ADD 50g OIL
FOR EACH
kg of
REFRIGERANT
The operation is carried out by following these steps:
x
stop the utilities and wait for the compressors to stop;
x
place the machine in OFF in the electronic control display;
x
close the general intake valve R1;
x
remove the internal pressure by acting on the RS1 and RS2 valves;
x
using the RS1 valve, load oil and at the same time aspirate with an empty pump on the service valve
RS2;
x
once loading is complete, close the RS1 and continue with the drain phase to the value previously
described;
x
remove the vacuum pump and related pipes from the service valve;
x
reopen the previously closed valves;
x
reactivate the machine in the ON position;
x
reactivate the utilities;
x
wait for the system to stabilise and for no alarms to be present;
ATTENTION: DO NOT load more than 250 g of oil at a time. If the necessary oil is higher, repeat the
above procedure.
The partly-completed machine does not include oil monitoring to check its presence inside the compressor
and the refrigerant circuit.
However, the electronic controller includes a function that facilitates return of the oil to certain working
conditions of the compressor by forcing the compressor to work at a fixed speed for a set time in order to
recover the oil lost along the refrigerant circuit.