The gas supply must be capable of handling the entire
gas load required at the location. Gas line sizing is
based on gas type, the pressure drop in the system,
the gas pressure supplied, and gas line type. For gas
pipe sizing, refer to the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, or the Natural Gas and Propane
Installation Code, CSA B149.1
For some tables, you will need to determine the cubic
feet per hour of gas required by dividing the gas input
by the heating value of the gas (available from the
local gas company). The gas input needs to include all
gas products at the location and the maximum Btu
usage at full load when all gas products are in use.
Use the table for your gas type and pipe type to find
the pipe size required. Ensure the maximum input rate
o the DHW system is used for calculating the gas pipe
sizing. The pipe size must be able to provide the
required cubic feet per hour of gas or the required
Btu/hr.
The information below is provided as an example. The
appropriate table from the applicable code must be
used.
Instructions: Enter values in empty boxes.
Rinnai Model Gas Input:
Additional Appliance Total Gas Input:
Heating Value of Gas:
Cubic Feet Per Hour (CFH):
ANSWER:
B
Btu/hr
C
Btu/ft
3
A
Btu/hr
(CFH)
=
FT
3
/HR
CFH
=
A
+
B
(CFH)
=
C
GAS PIPE SIZING CALCULATION WORKSHEET
Natural Gas
Schedule 40 Metallic Pipe
Inlet Pressure:
Less than 2 psi
Specific Gravity:
0.60
Information in table
obtained from NFPA 54,
ANSI Z223.1
-
2015.
Pressure Drop 0.5 in. w.c.
Nominal Pipe Size (in.)
1/2
3/4
1
1 1/4
Length in ft (meters)
Capacity in Cubic Feet of Gas per Hour
10 (3)
172
360
678
1,390
20 (6)
118
247
466
957
30 (9)
95
199
374
768
40 (12)
81
170
320
657
50 (15)
72
151
284
583
60 (18)
65
137
257
528
70 (21)
60
126
237
486
80 (24)
56
117
220
452
90 (27)
52
110
207
424
100 (30)
50
104
195
400
EXAMPLE
Rinnai Model Gas Input:
Additional Appliance Total Gas
Input:
Heating Value of Gas:
Cubic Feet Per Hour (CFH):
ANSWER:
B
65,000
BTU/HR
C
1,000
BTU/FT
3
A
160,000
BTU/HR
160,000+65,000
(CFH)
=
1000
225
FT
3
/HR
CFH
=
For this example, the pipe
diameter must be at least 3/4 in.
pipe size and 10 ft (3 m) in
length.
A
+
B
(CFH)
=
C
Содержание M Series
Страница 96: ...96 Rinnai M Series Condensing Boiler Combi Manual Heat Exchanger ...
Страница 98: ...98 Rinnai M Series Condensing Boiler Combi Manual Hydraulic Parts Pipes ...
Страница 101: ...Rinnai M Series Condensing Boiler Combi Manual 101 Electrical Components Solo Only ...
Страница 113: ...Rinnai M Series Condensing Boiler Combi Manual 113 ...
Страница 114: ...114 Rinnai M Series Condensing Boiler Combi Manual ...
Страница 122: ...122 Rinnai M Series Condensing Boiler Combi Manual 800000063 03 6 2019 ...