112
Rinnai M
-
Series Condensing Boiler Combi Manual
20.
The
Flash Memory Detected
screen
appears. Select
COPY
and Press
OK
.
21.
The following screen appears indicating
data parameters have been copied to the
Mainboard.
22.
The Home screen briefly appears on the
display and then the boiler turns off.
Home
screen
23.
After a few seconds, the boiler automatically
turns on and goes into
Airpurge active
mode.
Your psi values may differ than the values
shown in image.
24.
To remove the EEPROM key from the PC
Board:
a.
Disconnect power to the boiler
b.
Remove the front housing of the PC
Board.
c.
Remove the EEPROM key from the
connector.
25.
Reattach the PC Board front housing and
screw terminals. Clip the 6 tabs back into
place.
26.
Connect electrical power to the boiler. The
boiler will be back in normal operating
mode with the proper gas type
parameters.
27.
Replace the boiler front panel.
28.
The conversion process is complete. Verify
the O2 settings in minimum and maximum
input for your new gas type. See section
“10.
Commissioning
”
for detailed
instructions.
29.
Verify flame appearance as shown below
with the boiler in operation.
Flame
Rod
Blue Flame
SATISFACTORY
Front View
Front View
Flame
Rod
UNSATISFACTORY
Yellow or Green Flame
Figure 4
Содержание M Series
Страница 96: ...96 Rinnai M Series Condensing Boiler Combi Manual Heat Exchanger ...
Страница 98: ...98 Rinnai M Series Condensing Boiler Combi Manual Hydraulic Parts Pipes ...
Страница 101: ...Rinnai M Series Condensing Boiler Combi Manual 101 Electrical Components Solo Only ...
Страница 113: ...Rinnai M Series Condensing Boiler Combi Manual 113 ...
Страница 114: ...114 Rinnai M Series Condensing Boiler Combi Manual ...
Страница 122: ...122 Rinnai M Series Condensing Boiler Combi Manual 800000063 03 6 2019 ...