Rinnai cautions against installing the boiler in applications with venting in
different pressure planes. It is possible to have poor performance with this
installation.
Slope horizontal exhaust 1/4 in. per foot towards the boiler. DO NOT slope combustion air pipe
towards the boiler.
2 in. or 3 in.
PVC/CPVC
IPEX / Royal
Concentric
Side Wall
Termination
Configuration
2 in. or 3 in.
PVC/CPVC
IPEX /Royal
Concentric
Vertical
Termination
Configuration
2 in. or 3 in.
Schedule 40
PVC/CPVC
Snorkel
Termination
Configuration
2 in. or 3 in.
Schedule 40
PVC/CPVC
Standard
Upside Down
"U" Vertical
Termination
Configuration
2 in. or 3 in.
Schedule 40
PVC/CPVC
Elbow or Tee
Side Wall
Termination
Configuration
2 in. or 3 in.
Schedule 40
PVC/CPVC Tee
Vertical
Termination
Configuration
2 in. or 3 in.
PVC Low
Profile
Termination
Configuration
This configuration requires the use of
a Concentric Vent Termination.
This configuration requires the use of a
Concentric Vent Termination.
CAUTION
Tee not
permissible
for intake
termination
Tee not
permissible
for intake
termination
WARNING
Exhaust
Combustion
Air
Single
Pipe
Exhaust and
combustion air
MUST NOT be
brought together
into a single PVC
pipe using a pipe
fitting.
Unbalanced venting. Intake
and exhaust terminated on
different pressure planes.
Содержание M Series
Страница 96: ...96 Rinnai M Series Condensing Boiler Combi Manual Heat Exchanger ...
Страница 98: ...98 Rinnai M Series Condensing Boiler Combi Manual Hydraulic Parts Pipes ...
Страница 101: ...Rinnai M Series Condensing Boiler Combi Manual 101 Electrical Components Solo Only ...
Страница 113: ...Rinnai M Series Condensing Boiler Combi Manual 113 ...
Страница 114: ...114 Rinnai M Series Condensing Boiler Combi Manual ...
Страница 122: ...122 Rinnai M Series Condensing Boiler Combi Manual 800000063 03 6 2019 ...