Rinnai M
-
Series Condensing Boiler Combi Manual
75
PARA
Default
Range
Description
2.0.0
140°F
104
-
140°F
DHW setpoint temp (also achieved by pressing BACK and
turning dial on home screen)
2.0.3
194°F
176
-
194°F
Max Water Temp (absolute max)
Will limit outdoor reset curve settings
2.0.4
0
0
-
10,200
Will allow you to set higher than 10.2K but no effect
2.0.6
9°F/min
0
-
27°F/min
How quickly boiler reaches setpoint from cold start
2.2.4
ON
ON/OFF
AUTO function is the outdoor reset control. Changing this
to the off setting turns off outdoor reset and enables
simple setpoint CH supply temperature control. (Also
available from AUTO function in main menu (CH) or 4.2.1)
2.2.8
0
–
Combi
2
–
Solo
0=all Combi models
1=Solo boiler with 10K
Ω
NTC thermistor in DHW indirect tank
2=Solo boiler with aquastat in DHW indirect tank
2.4.9
0
-
5 to +5°F
Outdoor reset temp sensor correction
May need if outdoor reset is in direct sunlight, etc.
2.5.0
2
0=Eco (off)
1=Schedule
2=Comfort
DHW Comfort Mode
Also available from home screen (DHW)
2.5.7
1
0=OFF
1=ON
Anti
-
legionella Cycle (Solo models only)
2.6.0
OFF
ON/OFF
Activates manual mode for component testing
2.6.1
OFF
ON/OFF
Manual control of pump with burner off
2.6.2
OFF
ON/OFF
Manual control of fan with burner off
2.6.3
OFF
ON/OFF
Manual control of 3
-
way valve with burner off
2.7.0
OFF
ON/OFF
Forces chimney mode (same as button)
2.7.1
OFF
ON/OFF
Forces Air purge (or turn off –
same as holding BACK for 7
seconds)
Boiler Parameters
Содержание M Series
Страница 96: ...96 Rinnai M Series Condensing Boiler Combi Manual Heat Exchanger ...
Страница 98: ...98 Rinnai M Series Condensing Boiler Combi Manual Hydraulic Parts Pipes ...
Страница 101: ...Rinnai M Series Condensing Boiler Combi Manual 101 Electrical Components Solo Only ...
Страница 113: ...Rinnai M Series Condensing Boiler Combi Manual 113 ...
Страница 114: ...114 Rinnai M Series Condensing Boiler Combi Manual ...
Страница 122: ...122 Rinnai M Series Condensing Boiler Combi Manual 800000063 03 6 2019 ...