76
Rinnai M
-
Series Condensing Boiler Combi Manual
PARA
Default
Range
Description
2.8.0
NA
OK=YES
ESC=NO
Resets all parameters to factory defaults
(green button)
2.9.0
1
0=NO
1=NC
External Safety contact (LWCO, etc)
(NOTE: DO NOT USE OPTION 2)
2.9.1
1
0=OFF
1=ON
System (plant) frost protection, pump operation based
on outdoor temp sensor value
PARA
Default
Range
Description
4.2.0
1
0=Low Temp
1= High Temp
Outdoor reset curve presets
4.2.1
3
0=OFF
3=ON
Thermoregulation: outdoor temperature reset
Also available from AUTO function in main menu (CH)
or 2.2.4
DO NOT USE 1,2, or 4
4.2.2
LT=0.8
HT=2.0
LT=0.2
-
1.0
HT=1.0=3.5
Slope of outdoor reset curve (see separate slides),
depends on 4.2.0 setting
4.2.3
0
Depends on
curve settings
Heating curve offset (parallel shift)
4.2.5
LT=122°F
HT=185°F
LT=68
-
122°F
HT=68
-
185°F
Maximum supply temp (°F)
4.2.6
68°F
LT=68
-
122°F
HT=68
-
185°F
Minimum supply temp (°F)
PARA
Unit
Description
8.0.1
Hours
Total pump hours
8.0.3
Hours
Total hours boiler on power (electricity)
8.0.4
Hours
Total fan hours
8.0.5
Cycles
Total fan cycles
8.0.6
Cycles
Total CH flame ignitions
8.0.7
Cycles
Total DHW flame ignitions
Heating Parameters
Service Parameters
Содержание M Series
Страница 96: ...96 Rinnai M Series Condensing Boiler Combi Manual Heat Exchanger ...
Страница 98: ...98 Rinnai M Series Condensing Boiler Combi Manual Hydraulic Parts Pipes ...
Страница 101: ...Rinnai M Series Condensing Boiler Combi Manual 101 Electrical Components Solo Only ...
Страница 113: ...Rinnai M Series Condensing Boiler Combi Manual 113 ...
Страница 114: ...114 Rinnai M Series Condensing Boiler Combi Manual ...
Страница 122: ...122 Rinnai M Series Condensing Boiler Combi Manual 800000063 03 6 2019 ...