32
Rinnai M
-
Series Condensing Boiler Combi Manual
All terminations (horizontal and/or vertical)
must terminate 12 in. (0.30 m) above grade or
anticipated snow level.
12 in. (0.30 m)
Between terminals at same level
60 in. (1.52 m)
Between terminals at different levels
Note:
24 in. (0.61 m)
to wall or parapet
Inside
Corner
12 in.
(0.30 m)
12 in.
(0.30 m)
60 in. (1.52 m) vertically
between terminals
Vent Sizes
3 in. X 5 in.
2 in. X 4 in.
Boiler Model
Number
M060C
M090C, M120C, M160C
M060C
M090C, M120C, M160C
Vent Lengths
60 ft (18 m)
30 ft (9 m)
150 ft (46 m)
140 ft (43 m)
•
45° elbow is equivalent to 3 ft (1 m)
•
90° elbow is equivalent to 6 ft (2 m)