Installation Guidelines
•
What You
’
ll Need
•
Items Included
•
Choose an Installation Location
•
Mount the Boiler to the Wall
THIS SECTION IS INTENDED
FOR THE INSTALLER
Installer qualifications: A trained and qualified
professional must install the appliance,
inspect it, and leak test the boiler before use.
The warranty will be voided due to any
improper installation. The trained and
qualified professional should have skills such
as: Gas sizing; Connecting gas lines, water
lines, valves, and electricity; Knowledge of
applicable national, state, and local codes;
Installing venting through a wall or roof; and
training in installation of condensing boilers.
Training for Rinnai Condensing Boilers is
accessible online at
www.trainingevents.rinnai.us.
Topics in this section
4
•
This boiler is certified for installation in
residential and commercial applications.
•
This boiler is suitable for combination
water heating and central heating.
•
The installation must conform with local
codes or, in the absence of local codes,
with the
National Fuel Gas Code, ANSI
Z223.1/NFPA 54
, or the
Natural Gas and
Propane Installation Code, CSA B149.1
. If
installed in a manufactured home, the
installation must conform with the
Manufactured Home Construction and
Safety Standard, Title 24 CFR, Part 3280
and/or
CAN/SCA Z240 MH Series, Mobile
Homes
.
•
The appliance, when installed, must be
electrically grounded in accordance with
local codes or, in the absence of local codes,
with the
National Electrical Code, ANSI/
NFPA 70
, or the
Canadian Electrical Code,
CSA C22.1.
•
The appliance and its main gas valve must
be disconnected from the gas supply piping
system during any pressure testing of that
system at test pressures in excess of 1/2 psi
(3.5 kPa) (13.84 in W.C.). For system testing
at pressures less than or equal to 1/2 psi
(3.5 kPa) (13.84 in W.C.) the appliance must
be isolated from the gas supply piping by
closing its individual manual shutoff valve.
•
You must follow the installation instructions
and those in section
“5.
Venting
”
for
adequate combustion air and exhaust.
•
If this boiler
’
s DHW system is connected to a
closed water supply system, such as one
having a backflow preventer in the cold
water supply line, means shall be provided
to control thermal expansion. Contact the
water supplier or local plumbing inspector
on how to control thermal expansion.
•
Should overheating occur or the gas supply
fail to shut off, turn off the manual gas
control valve to the appliance.
•
Combustion air must be free of chemicals,
such as chlorine or bleach, that produce
fumes. These fumes can damage
components and reduce the life of your
appliance.
•
Where required by the authority having
jurisdiction, the installation must comply
with the Standard for Controls and Safety
Devices for Automatically Fired Boilers,
ANSI/ASME CSD
-
1.
Содержание M Series
Страница 96: ...96 Rinnai M Series Condensing Boiler Combi Manual Heat Exchanger ...
Страница 98: ...98 Rinnai M Series Condensing Boiler Combi Manual Hydraulic Parts Pipes ...
Страница 101: ...Rinnai M Series Condensing Boiler Combi Manual 101 Electrical Components Solo Only ...
Страница 113: ...Rinnai M Series Condensing Boiler Combi Manual 113 ...
Страница 114: ...114 Rinnai M Series Condensing Boiler Combi Manual ...
Страница 122: ...122 Rinnai M Series Condensing Boiler Combi Manual 800000063 03 6 2019 ...