Rinnai
41
RD
V 600_700 OIM
COMMISSIONING INSTRUCTIONS
4. Press the 'UP' button
or 'DOWN' button
to adjust to the required value if values are different to those in
the table below.
5. Press the 'Set Button'
, once to save the setting. The display
, should now be displaying
, (Main burner
stage 7).
6. Press the 'UP' button
or 'DOWN' button
to adjust to the required value, If the pressure is already correct
or when the desired pressure is achieved press the 'Set Button'
, once to save the setting.
7. The display
, will now show
. If the display does not change to
there was an error in pressure setting
and the pressure setting procedure should be repeated from step 1 onward after turning the appliance 'OFF'
8. With the display
, showing
Press the heater ON/OFF button
.
9. Setting main burner pressure is now complete. Remove the manometer hose and replace the inlet test point
screw
. Check for leaks using soapy water solution.
Step 3 . Checking and setting Pilot burner pressure.
1. Remove the pilot flame gas test point screw
, and connect a positive pressure manometer hose.
2. Press the heater ON/OFF button
to start the ignition sequence, the appliance will ignite normally.
3. Press the 'TEST' button
, twice on the PCB control panel, the igniter will spark and the appliance will light to
its lowest setting, (Main burner - stage 1), and the display
, will show
.
4. Adjust the pilot flame gas pressure to the value for the gas type as listed in the table below via the 'Pilot Flame
Pressure Adjustment' screw
.
5. Press the heater ON/OFF button
, once to stop the appliance operation. Disconnect the manometer hose
and replace the pilot flame gas test point crew
.
6. Check for gas leaks using soapy water, setting or checking pilot burner pressure is now complete.
Natural Gas
Propane Gas
Model
RDV600ER
RDV700ER
RDV600ER
RDV700ER
P L (stage 1)
0.20 kPa
0.20 kPa
0.50 kPa
0.50 kPa
P H (stage 7)
0.90 kPa
0.86 kPa
1.95 kPa
1.92 kPa
Refer to chart for the correct gas settings, (data plate values override values printed in this instruction).
Natural Gas
Propane Gas
Pilot Flame Pressure
1.00 kPa
2.00 kPa
Refer to chart for the correct gas settings, (data plate values override values printed in this instruction).
The Requirements of AS / NZS 5601 include:
a. checking whether mechanical extraction ventilation draws air through flue systems or
chimneys or not. If yes, this will most likely result in combustion product spillage from
appliances during their operation.
b. checking whether the operation of appliances and flue systems or chimneys is satisfactory.
c. a method for determining the additional fixed ventilation area required to counteract the
effect of mechanical extract ventilation.
Always check gas pressure values to those recorded on this appliances data plate, values on the
data plate override values printed in this instruction.
8
9
11
13
8
9
11
13
13
12
1
2
12
6
13
3
12
2
NOTE
WARNING