Further Settings & Programming:
All changes to these settings must be completed by a licensed electrician
VR1: Total Working Time Adjustment
Rotate clockwise to increase, counter-clockwise to decrease. Total time can be set to 10
seconds minimum, and 90 seconds maximum.
The default setting is at maximum.
VR2: Unused
VR3: Stall Force Adjustment
Rotate clockwise to increase, counter-clockwise to decrease.
The default setting is at maximum.
When stall force is enabled (DIP switch 7 is at the ON position), the motor will detect obstacles
and impacts to the gate. If this is during opening, the gate will stop, if this is during closing the
gate will stop, and then re-open.
Note: If the stall force is too low,
the gate will stop or reverse very easily while there is no
obstruction, or if there is additional resistance such as strong wind, rain or snow
. If the stall
force is set too high,
some impacts may not be detected, and injury or damage could occur.