Analog Output Setting (Analog Models Only)
Write the weight in the registers 40045 (Weight value corresponding to the Full Scale of analog output H) and 40046 (Weight
value corresponding to the Full Scale of analog output L), or write the weight in the registers 40043 (Weight value
corresponding to the ZERO of the analog output H) and 40044 (Weight value corresponding to the ZERO of the analog output
L). After writing the value, send the command 99 from the Command Register to save it to EEPROM memory.
The output status can be read at any time but can be set (written) only if the output has been set as
NOdbUS
or
(
); otherwise, the outputs will be managed according to the current weight status
with respect to the relevant setpoints.
Status Register (40007)
Bit 0
Cell Error
Bit 8
Net weight negative sign
Bit 1
AD Convertor Malfunction
Bit 9
Peak weight negative sign
Bit 2
Maximum weight exceeded by 9 divisions
Bit 10
Net display mode
Bit 3
Gross weight higher than 110% of full scale
Bit 11
Weight stability
Bit 4
Gross weight beyond 999999 or less than -999999
Bit 12
Weight /-¼ of a division around ZERO
Bit 5
Net weight beyond 999999 or less than -999999
Bit 13
—
Bit 6
—
Bit 14
—
Bit 7
Gross weight negative sign
Bit 15
—
Table 3-36. Status Register (40007) (Analog Model)
INPUTS REGISTER (40029)
(Read Only)
OUTPUTS REGISTER (40030)
(Read and Write)
Bit 0
INPUT 1 Status
Bit 0
OUTPUT 1 Status
Bit 1
INPUT 2 Status
Bit 1
OUTPUT 2 Status
Bit 2
—
Bit 2
OUTPUT 3 Status
Bit 3
—
Bit 3
—
Bit 4
—
Bit 4
—
Bit 5
—
Bit 5
—
Bit 6
—
Bit 6
—
Bit 7
—
Bit 7
—
Bit 8
—
Bit 8
—
Bit 9
—
Bit 9
—
Bit 10
—
Bit 10
—
Bit 11
—
Bit 11
—
Bit 12
—
Bit 12
—
Bit 13
—
Bit 13
—
Bit 14
—
Bit 14
—
Bit 15
—
Bit 15
—
Table 3-37. Input and Output Registers (Analog Model)
Note