Configuration
© Rice Lake Weighing Systems
●
All Rights Reserved
17
Parameter
Options
Description
(Communication
Port)
Disables any type of communication.
MODBUS-RTU protocol; possible addresses: from 1 to 99 (
)
ASCII bidirectional protocol; possible addresses: from 1 to 99 (
)
NOdU6
NOdTd
Continuous weight transmission protocol (
), at the frequency set in HERTZ parameter
(from 10 to 300).
MOd t
set: PARITY = none STOP = 1
MOd td
set: PARITY = none STOP = 1
Continuous weight transmission protocol, streams net and gross (see
)
Set: BAUD = 9600 PARITY = none STOP = 1
Continuous weight transmission protocol, streams net and gross including decimal. (
) Set:
BAUD = 9600 PARITY = none STOP = 1
Continuous weight transmission protocol (see
Set: BAUD = 9600 PARITY = none STOP = 1
When the remote display is set to gross weight:
- if the instrument displays the gross weight, the remote display shows the gross weight.
- if the instrument shows the net weight the remote display shows the net weight alternated with the message
net
2400
4800
9600
*
*
1
9200
38400
115200
Transmission speed.
1-99
1
*
Instruments address
Maximum Transmission Frequency – set when the
transmission protocol is selected.
1
0Hz
*
*
20Hz
Max setting with min 2400 baud rate
30Hz
40Hz
Max setting with min 4800 baud rate
50Hz
60Hz
70Hz
80Hz
Max setting with min 9600 baud rate
100Hz
Max setting with min 19200 baud rate
200Hz
Max setting with min 38400 baud rate
300Hz
Max setting with min 38400 baud rate
0-200 msec
*
Delay in milliseconds which elapses before the instrument replies
nOnE
*
*
EUEn
Odd
parity none
even parity
odd parity
1
*
*
2
Stop bit
* Indicates default value.
Table 2-7. Serial Communications Menu Parameters