2.1.3.5.2. Analog inputs
The configuration of the analog input corresponds to the setup of the analog outputs.
Choose the desired units for the analog input (0/1-5 volt) from the following units:
V, mA, kg/l, °C, ml/min, m3/min, bar, bara, psi, mPas.
After pressing
Next,
it is possible to set the input signal range to 1 - 5 Volts or to 0 - 5 Volts. Next
select the lowest and highest values for this range (ie. 0/1 and 5)
Note:
For use as current loop input you have to connect a resistor of 250 Ohm.
example:
250 Ohm
0/ 4 - 20 m A
current source