Specifications of the TRITON
Models
GHE (gas high efficiency gas) 80 and 100 gallon (tank capacity)
Powered direct vent; sealed combustion; fully condensing; ASME rating options
on all inputs; power vent options on all inputs.
Fuel Type
Natural and L.P. gas; thermal efficiency based on model
Gallon Capacity
80 and 100 gallons
Rated Gas Input (Btu/Hr.)
130,000; 150,000, 160,000’; 199,000; 250,000; 300,000; 350,000; 399,000
Ignition System
Spark ignition to main burner; no pilot of any kind
Heat Exchanger
Down fired, multi-pass heat exchanger
Diagnostics
Nonvolatile storage of heater settings and fault history. Diagnostic codes provided
through an onboard LCD display consisting of information on power to the control,
control status, fault codes and system settings.
Installation
Indoor only
Gas Connection
1
/
2
“ and
3
/
4
” NPT Female
Inlet Gas Pressure
Natural Gas Min. 3.5" w.c. Max. 10.5" w.c.
L.P. Gas Min. 11.0" w.c. Max. 13.0" w.c.
High Altitude
Units rated to 8,999ft.
Water Connection
2” NPT inlet/outlet – side connect – front and rear
1.5” for Top (Plugged from factory)
Vent Material Allowed
Polypropylene, PVC, ABS, CPVC plastic pipe options
130-160kbtu – 2” (, 3”, 4”, & 6” venting options
199kbtu – 2” (, 3”, 4”, & 6” venting options
250-399kbtu – 3”, 4” & 6” venting options
SEE USE AND CARE MANUAL
Maximum Vent Lengths
SEE USE AND CARE MANUAL
Noise Level
60 db @ 15 feet (max) using test ANSI S12.34/ISO 3744
Water Temperature
Factory Setting
120°F
Digital Thermostat (adjustable)
1 degree increments
85°F to 185°F
Temperature Differential
Factory Setting of
User selectable from 1°F to 30°F
Electrical
Electrical Rating
120 VAC 50/60Hz, 7 Amps
Wire
3 (three) wire (hot, neutral, ground)
Earth Ground Sensitive
Yes
Polarity Sensitive
Yes
Safety Devices
Temperature and Pressure Relief Valve – 150 PSI or 210
0
F
Venting Over Temperature Switch; trips at 160
0
F; automatic reset
Energy Cut Off for high water temperature; trips at 205
0
F (auto reset) +- 3
0
F
Flame Rectification - The presence of a flame is measured via a flame rod that points
into the flame. Control measures => 8.0 micro amp (uA)
Fuse protected main controller
5
Triton
Service Manual SVC1020T ; Rev 4
80 and 100 gallon chassis
Содержание TRITON
Страница 7: ...Component Parts of the TRITON 7 Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis ...
Страница 8: ...Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis Wiring and Schematic Diagram 8 ...
Страница 9: ...Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis Connection Diagram 9 ...
Страница 14: ...Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis User Interface 14 ...
Страница 15: ...Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis User Interface 15 ...
Страница 16: ...Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis User Interface 16 ...
Страница 17: ...Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis User Interface 17 ...
Страница 20: ...Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis Sequence of Events 20 ...
Страница 21: ...Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis Sequence of Events 21 ...
Страница 46: ...4 6 Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis Notes ...
Страница 57: ...BACnet Configurations Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis 5 7 ...