Insert your other meter lead into the molex connector location for the
wire associated with the suspect anode as shown in bottom photo.
•
Resistance reading should be less than 20 ohms.
If reading is higher
than 20 ohms replace wiring harness
NOTE: The anode rod power wire harness has 4 wires in the molex.
GREEN = GROUND
RED = UPPER ANODE
BLUE = MIDDLE ANODE
ORANGE = LOWER ANODE
Note: Turn off power to water heater
.
•
With anode power wire disconnected, insert one meter lead into the wire as
shown.
•
Locate the
anode control module
.
•
Disconnect the
anode power lead harness
from the
anode control module
.
NOTE
:
If this is a new install, and no issues were found during anode “Overload” and/or “Pre-Overload”
testing, see next page.
Triton
Service Manual SVC1020T ; Rev 4
80 and 100 gallon chassis
4 5
Troubleshooting Error Codes
Содержание TRITON
Страница 7: ...Component Parts of the TRITON 7 Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis ...
Страница 8: ...Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis Wiring and Schematic Diagram 8 ...
Страница 9: ...Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis Connection Diagram 9 ...
Страница 14: ...Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis User Interface 14 ...
Страница 15: ...Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis User Interface 15 ...
Страница 16: ...Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis User Interface 16 ...
Страница 17: ...Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis User Interface 17 ...
Страница 20: ...Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis Sequence of Events 20 ...
Страница 21: ...Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis Sequence of Events 21 ...
Страница 46: ...4 6 Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis Notes ...
Страница 57: ...BACnet Configurations Triton Service Manual SVC1020T Rev 4 80 and 100 gallon chassis 5 7 ...