Radio Frequency Systems
BD210WLP Series Air Dryer User’s Guide
Page 94 of 101
100518832 – Rev. B
High Compressor Last
Run Time Alarm set
point higher that the
default of 3:00 minutes
Verify High
Compressor Last Run
Time Alarm set point
(section 9.9 )
Allow the compressor
to run longer than the
verified set point
(section 9.9 )
Defective Control
Board
Verify that the
compressor has run
longer than the verified
High Compressor Last
Run Time Alarm set
point (above)
Replace Control Board
(section 11.1 ) if the
compressor runs longer
than the verified High
Compressor Last Run
Time Alarm set point
by 1 minute or more
and fails to create an
alarm.
13.20 Compressor Rapid ON/OFF Cycling
Possible Cause
Check
Corrective Action
Defective control board Measure voltages at
control board
(section 9.3 )
If measurements are
incorrect, replace
control board (section
11.1 )
13.21 Contacting Altec AIR Technical Support
Please read the Before You Call Altec AIR section (13.2 )
Once you have exhausted all of the potential problems and solutions covered in the
Troubleshooting Your Dryer
section, and you still require further assistance to correct
a problem, contact RFS Technical Support:
(800) 521-5351
(option 1)
Have the following information available:
Trouble Ticket # (if following-up on a previous call)
:
Содержание BD210WLP Series
Страница 2: ......