Model MMU-1600G Series Op Man - Ver 1.07.23 - Rev 20151026DL
Page 44 of 58
4.6.2.2.3 Factory Unit Information
See Section
4.6.1.2
4.6.2.2.4 Comm Port Settings
Use the left (◄) or right (►) pushbutton to navigate to the desired setting to change. Use the up (▲) or down (▼)
pushbutton to change the highlighted setting. Press the
ENTER
pushbutton or the
ESCAPE
pushbutton to exit to the
previous display.
BAUD RATE
– The Communications Port Baud Rate setting can be set to any of the following values:
300
,
1200
,
2400
,
4800
,
9600
,
19200
,
38400
, or
57600
. The factory default setting is
57600
.
STOP BITS
– The Communications Port Stop Bits setting can be set to
1
or
2
. The factory default setting is
1
.
PARITY
– The Communications Port Parity setting can be set to
NONE
,
ODD
,
or
EVEN
. The factory default setting is
NONE
.
4.6.2.2.5 Ethernet Settings
See Section
4.6.1.3
4.6.3 Logging System
MENU TEXT
MENU FUNCTION
VIEW LOGS
View monitor logs.
CLEAR LOGS
Clear individual logs.
CLEAR ALL LOGS
Clear all logs.
LOGGING THRESHOLDS
View and/or edit the AC Logging Threshold settings of high voltage alarm,
low voltage alarm, and power interrupt duration.
4.6.3.1 View Logs
MENU TEXT
MENU FUNCTION
VIEW DATE & TIME LOG
View the Date & Time log.
VIEW AC LINE LOG
View the AC Line log.
VIEW RESETS LOG
View the Resets log.
VIEW CONFIGURATIONS LOG
Access the View Configurations Log menu.
VIEW PRIOR FAULTS LOG
View the Prior Faults log.
VIEW SIGNAL SEQUENCE LOG
View the Signal Sequence log.
4.6.3.1.1 View Date & Time Log
The monitor records the thirty (30) most recent date and/or time changes in the Date & Time Log. Original Date and Time,
New Date and Time, and Up Time are recorded. This display is view only.
Use the left (◄) or right (►) pushbutton and the up (▲) or down (▼) pushbutton to scroll through the entries. Press the
ENTER
pushbutton or the
ESCAPE
pushbutton to exit.
4.6.3.1.2 View AC Line Log
The monitor records the fifty (50) most recent changes in AC line status in the AC Line Log. Date and Time, Event Type
(Power Up, Power Down, Low Voltage, Low Voltage Recovery, Low Voltage Alarm, Low Voltage Alarm Recovery, High
Voltage Alarm, High Voltage Alarm Recovery, and Power Interrupt), AC Line Voltage / Event Duration, and AC Line
Frequency are recorded. This display is view only.
Use the left (◄) or right (►) pushbutton and the up (▲) or down (▼) pushbutton to scroll through the entries. Press the
ENTER
pushbutton or the
ESCAPE
pushbutton to exit.
4.6.3.1.3 View Resets Log
The monitor records the twenty (20) most recent resets in the Resets Log. Date and Time, Fault Cleared and Reset Source
are recorded. This display is view only.
Press the
ENTER
pushbutton to view the Resets Log. Use the left (◄) or right (►) pushbutton and the up (▲) or down (▼)
pushbutton to scroll through the entries. Press the
ENTER
pushbutton or the
ESCAPE
pushbutton to exit.