background image

 

Model MMU-1600G Series Op Man - Ver 1.07.23 - Rev 20151026DL 

Page 13 of 58 

 

2.4.11  Factory Settings 

The monitor is configured at the factory during final test.  Data set at the factory includes:  Model Number, Serial Number, 
Manufacture  Date,  Real  Time  Clock  setting,  Support  for  Flashing  Greens,  Enhanced  Support  of  Econolite  Controllers, 
Support for a Diagnostic LCD.  The Up Time Accumulator is initialized to zero prior to final testing.  Changes to Support for 
Flashing  Greens,  Enhanced  Support  of  Econolite  Controllers,  and  Support  for  a  Diagnostic  LCD  are  logged  in  the 
configuration log. 

2.4.12  User Unit Information 

The monitor has non-volatile memory that can be used to store the following user unit information: 40 character Location ID, 
4 character Unit ID, and 5 character Agency ID.  All of these IDs can consist of any alpha-numeric characters.  Upper and 
lower case characters can be used but all lower case will be displayed as uppercase on the front panel graphic display. 

2.5 

FAULT MONITORING 

2.5.1  Conflict Monitoring 

Configuration:

 The jumpers installed on the Program Card determine permissive (non-conflicting) channels.  A jumper in 

the row labeled “2” and the jumper hole pair labeled “6” would make Channels 2 and 6 permissive with each other.  This is a 
two-way relationship.  If channel 2 is programmed as permissive with channel 6 then channel 6 is automatically permissive 
with channel 2.  The testing defaults for this feature are determined by the jumpers installed on the program card.  Typically 
no jumpers are installed during automated testing. 

Test  Preformed:

  While  a  channel  has  a  Green,  Walk,  or  Yellow  display  active,  the  channel  is  tested  to  see  if  a  non-

permissive channel has a Green, Walk, or Yellow display active at the same time.  If concurrently active conflicting displays 
are detected a conflict timer is started.  If the conflict goes away the conflict timer is stopped (it is not cleared) and a non-
conflict timer is started.  If the conflict reappears the non-conflict timer is reset to zero and the conflict timer continues timing 
from its prior value.  If the conflict timer reaches 300 milliseconds or more the monitor will latch a conflict fault.  If the non-
conflict timer reaches 666 milliseconds  the conflict timer is reset to zero  and the conflict is ignored.  The normal  voltage 
thresholds for this test are: Reds – ON when above 70V

RMS

 and OFF when below 50V

RMS

, Greens / Yellows / Walks – ON 

when above 25V

RMS

 and OFF when below 15V

RMS

Fault Action:

 The monitor transfers the Output relay contacts to the fault condition (continuity between the Normally Open 

and Common contacts), illuminates the 

CONFLICT

 indicator on the front panel, and sets the Conflict bit (bit 65) of the Type 

129 Frame to 1.  The Signal Sequence log and the Prior Faults log will record this fault. 

Resetting the Fault:

 The monitor remains in this fault condition until the unit is reset by the activation of the front panel 

reset pushbutton or the activation of the reset input.  Power loss or power interruption will not reset this fault.  The Reset log 
will record the resetting of this fault. 

Modifying Inputs:

 None

 

Feature Interactions: 

Flashing Don’t Walk Monitoring

: When Flashing Don’t Walk Monitoring is enabled and channels have programmed as 

active for this feature, a flashing red on a channel  with this feature active  will be included in the displays checked  for 
conflicts.  A conflict with a flashing red must exist for 1500 milliseconds to create a conflict fault. 

Flashing Yellow Arrow Left Turns

: When Flashing Yellow Arrow (FYA) is enabled and FYA Ignore Yellow Conflict is 

enabled and a Channel has an  FYA checked as a child channel  that  conflicts  with this channel a Yellow  in the parent 
channel and a Yellow in the child channel being active at the same time will be ignored as a conflict when the Yellow of 
the parent channel is terminating a flashing Yellow arrow.  Also, when Flashing Yellow Arrow (FYA) is enabled and Per 
Channel Red Enables is enabled and the channel Red Enable is disabled and Dual Indication / Field Check for the channel 
is disabled and Minimum Yellow Change Disable for the channel is not jumpered on the Program Card and the channel 
has  the  actual  flashing  yellow  arrow  display  the  monitor  will  ignore  the  unused  Green  or  Yellow  of  that  channel  for 
conflict tests. 

LED Thresholds

: When LED Thresholds is enabled the monitor senses Greens, Yellows, Reds, and Walks as ON when 

their voltage is above 25V

RMS

 and OFF when below 15V

RMS

 for the conflict test. 

2.5.2  Red Fail Monitoring 

Configuration

:  All channels will be monitored for the red fail fault unless the Per Channel Red Enables feature is enabled.  

When  Per  Channel  Red  Enables  are  enabled  only  channels  that  have  been  programmed  as  active  for  this  feature  will  be 
included in the displays checked for red fail.  The testing defaults for this feature are Per Channel Red Enables is disabled 
and all channels enabled for red fail testing. 

Test  Preformed

:  When  a  channel  has  no  displays  active  (Red,  Yellow,  Green,  or  Walk)  a  red  fail  timer  is  started.    If  a 

display turns on for the channel the red fail timer is stopped (it is not cleared) and a non-red fail timer is started.  If the no 

Содержание MMU-1600G Series

Страница 1: ...NO A E Reno A E 4655 Aircenter Circle Reno Nevada 89502 USA Telephone 775 826 2020 Facsimile 775 826 9191 Internet www renoae com E mail contact renoae com NEMA TS 2 20 NEMA TS 2 2003 Malfunction Mana...

Страница 2: ...nagement Unit was designed built inspected and tested to ensure its proper operation It is Reno A E s recommendation that each Malfunction Management Unit be tested at least annually to ensure complia...

Страница 3: ...2 4 2 Minimum Flashing Indication 11 2 4 3 Reset 11 2 4 4 Type 16 Only Mode 11 2 4 5 COM Port 11 2 4 6 Ethernet Port 11 2 4 7 Temperature Sensor 12 2 4 8 Real Time Clock 12 2 4 9 Up Time Accumulator...

Страница 4: ...Upgrade Pending 35 4 5 Voltage Displays 35 4 6 Main Menu 35 4 6 1 Identification Menu 36 4 6 1 1 User Unit Information 36 4 6 1 2 Factory Unit Information 36 4 6 1 3 Ethernet Settings 36 4 6 2 Configu...

Страница 5: ...atus Menu 47 4 6 5 1 Channels 1 6 47 4 6 5 2 Channels 7 12 47 4 6 5 3 Channels 13 16 47 4 6 5 4 Other AC and Miscellaneous Inputs 47 4 6 5 5 DC Inputs 47 4 6 6 Diagnostic Info 48 4 6 6 1 LED Test Sett...

Страница 6: ...Walk inputs associated with a channel shall be considered as that channel being active The signal monitor portion of the monitor is also capable of checking for the absence of any required signal vol...

Страница 7: ...to the chassis of the unit This input is not connected to Logic Ground or AC Neutral within the unit Typical Connection Cabinet Earth Ground 2 1 4 Field Terminals Reds Yellows Greens and Walks The fi...

Страница 8: ...ut Type Select input 24V Monitor Inhibit input Local Flash Status input and Port 1 Disable input as well as the Port 1 SDLC communications signals This termination Connector A Pin T is not connected t...

Страница 9: ...binet Interlock The monitor has two terminals internally connected to indicate the presence of the unit to external circuitry These terminals are identified as Cabinet Interlock A Connector A Pin CC a...

Страница 10: ...een pairs of holes for Minimum Yellow Change Disable programming jumpers The sixteen jumper hole pairs are logically labeled for easy identification of the channel numbers A soldered wire jumper in a...

Страница 11: ...ew reset input to the monitor Activation of either reset will cause all of the front panel LEDs to turn on for 300 milliseconds The only intended purpose of the reset input is to facilitate automated...

Страница 12: ...rational SDLC bus any time setting entered via the front panel will be overwritten by the Controller Time setting If it is necessary to change the Real Time Clock setting in a monitor that is being us...

Страница 13: ...transfers the Output relay contacts to the fault condition continuity between the Normally Open and Common contacts illuminates the CONFLICT indicator on the front panel and sets the Conflict bit bit...

Страница 14: ...ow Arrow Left Turns When Flashing Yellow Arrow FYA Left Turns are enabled and a Channel has an FYA setting of G for one of its child channels then the Green of the child channel will be included in th...

Страница 15: ...l has a Green and a Yellow display active a dual indication timer is started If one of the indications turns off the dual indication timer is stopped it is not cleared and a single indication timer is...

Страница 16: ...ft Turns When Flashing Yellow Arrow FYA Left Turns are enabled and a channel has an FYA setting with a setting of G or Y for one of its child channels then the Yellow of the channel will be used for t...

Страница 17: ...f this fault Modifying Inputs Red Enable All field check testing will be disabled when this input is below 70VRMS Port 1 Disable All field check testing will be disabled when this input is below 8VDC...

Страница 18: ...est Preformed A voltage greater than 22VDC applied to the 24 Volt Monitor II input is recognized as adequate for proper operation A voltage of less than 18VDC is recognized as inadequate for proper op...

Страница 19: ...contacts to the fault condition continuity between the Normally Open and Common contacts illuminates the LOC FLASH indicator on the front panel and sets the Local Flash bit bit 79 of the Type 129 Fra...

Страница 20: ...cal Use This feature is used to provide additional fault checking for Flashing Don t Walk displays Without this feature a flashing Red input is never checked for conflicts 2 6 2 Co Channel Monitoring...

Страница 21: ...re the unused Green or Yellow of that channel for conflict tests Red Fail Normal red fail testing ensures that at least one display is active for a channel With this feature active any channel with a...

Страница 22: ...elow 15VRMS Reds are ON when their voltage is above 70VRMS and OFF when below 50VRMS With LED thresholds the monitor senses Greens Yellows Reds and Walks as ON when their voltage is above 25VRMS and O...

Страница 23: ...ration is allowed Typical Use This feature is useful when it is desirable to ignore a command to begin flash operation of the intersection This may come from a Time Clock or an output of the Controlle...

Страница 24: ...g The AC Line Log records the 50 most recent changes in AC line status Data recorded Date Time Stamp Event Type Power Up Reset Low Voltage Low Voltage Recovery Shutdown Low Voltage Alarm Low Voltage A...

Страница 25: ...ype 129 Frame being set to 1 NOTE Port 1 communications may not be possible during certain diagnostic failures 2 8 1 Memory The monitor verifies all memory elements on power up or upon reset of a Diag...

Страница 26: ...DSP Timeout 6 0020h The DSP did not respond to a request for data in the required amount of time Ethernet Port Error 7 0040h The interface hardware for the Ethernet port is not functioning properly D...

Страница 27: ...metal shell D subminiature receptacle with gold plated female contacts and nuts for retaining screws ETHERNET CONNECTOR High speed 10Base T 100Base TX RJ 45 network jack optional 3 2 ELECTRICAL POWER...

Страница 28: ...TIMING FUNCTIONS START DELAY 2 0 sec 0 5 sec MINIMUM FLASH 6 to 16 sec 1 sec PORT 1 FAIL Typical 300 msec FIELD CHECK FAIL Typical 1000 msec CONFLICT No Fault 200 msec Detect 450 msec Typical 300 mse...

Страница 29: ...2 Only I Channel 10 Walk I b Channel 10 Yellow I Channel 10 Yellow I c Channel 9 Yellow I Channel 9 Yellow I d Channel 8 Yellow I Channel 8 Yellow I e Channel 7 Yellow I Channel 7 Yellow I f Channel 6...

Страница 30: ...ype 16 Only I U Start Delay Relay N C Open During Start Delay O Start Delay Relay N C Open During Start Delay O V Channel 10 Red I Channel 10 Red I W Channel 14 Red I Channel 14 Red Type 16 Only I X C...

Страница 31: ...served Reserved 20 5 9 5 10 5 11 20 Reserved Reserved Reserved 21 5 12 5 13 5 14 21 Minimum Flash Minimum Flash Minimum Flash 22 5 15 5 16 6 7 22 Minimum Flash 24V Latch CVM Latch 23 6 8 6 9 6 10 23 R...

Страница 32: ...wer is low Type 12 LED ON Type 12 Mode OFF Type 16 Mode Blip Type 16 Only Receive Transmit Receive ON A valid SDLC frame addressed to the monitor was received Transmit ON A SDLC frame was transmitted...

Страница 33: ...Prior Date Time Functions Clear Logs Clear All Logs Logging Thresholds View Prior Faults Log View Signal Sequence Log Clear Date Time Log Clear AC Line Log Clear Resets Log Clear Configurations Log Cl...

Страница 34: ...button will display the Configuration Shortcuts menu Right Pushbutton The pushbutton labeled is used to navigate through menu selections or settings being viewed If the setting being viewed can be ch...

Страница 35: ...toring Menu and select Save Changes 4 4 4 Upgrade Pending When new firmware has been downloaded in to the monitor the Run Time display will indicate that there is a pending upgrade and that you need t...

Страница 36: ...d is typically used to store the intersection that the monitor is installed at example VIRGINIA AVE LONGLEY AVE UNIT ID This text field is four 4 characters long The user can edit this field This fiel...

Страница 37: ...s monitor to the factory defaults WIZARD Access the configuration wizard that can be used to automatically configure most settings in the monitor 4 6 2 1 1 Start Configuration Before a change can be m...

Страница 38: ...an monitoring settings FYA LEFT TURNS View and or modify the Flashing Yellow Arrow Left Turn settings CO CHANNELS View and or modify the Co Channel settings THRESHOLDS View and or modify threshold set...

Страница 39: ...ushbutton to toggle the setting Press the ESCAPE pushbutton to exit See Section 2 6 5 for more detailed information on Per Channel Red Enables PER CHAN RED EN CO CHAN When this feature is enabled the...

Страница 40: ...f heads with more than 3 sections This feature is mutually exclusive with FYA Enable If FYA Enable is set to YES you will not be able to access this screen You will need to go the FYA Left Turns displ...

Страница 41: ...atus of an optional external watchdog output from a Controller Unit or other external cabinet device See Section 2 5 13 for more information The factory default for this feature is NO TYPE 16 ONLY Whe...

Страница 42: ...tored O Overlap or Other Used channels not covered by the above three options Unused 4 6 2 1 10 3 Left Turn Configurations LEFT TURN TYPE Select the type of left turn You will get this screen for ever...

Страница 43: ...ts given to the wizard 4 6 2 1 10 6 Almost Done If there were no warning or you ignored all warnings you will get the Almost Done screen Pressing ENTER here will create a new configuration based on th...

Страница 44: ...CONFIGURATIONS LOG Access the View Configurations Log menu VIEW PRIOR FAULTS LOG View the Prior Faults log VIEW SIGNAL SEQUENCE LOG View the Signal Sequence log 4 6 3 1 1 View Date Time Log The monito...

Страница 45: ...re each of the previous nine 9 monitor configurations stored in the Configurations Log to the current monitor configuration Date and Time the total number of Different Features a list of the Different...

Страница 46: ...CONFIGURATIONS LOG Clear the Configurations log CLEAR PRIOR FAULTS LOG Clear the Prior Faults log CLEAR SIGNAL SEQUENCE LOG Clear the Signal Sequence log For each of these screens use the arrow pushb...

Страница 47: ...eld inputs for channels 13 through 16 OTHER AC MISC INPUTS View the real time voltages on the AC and Red Enable inputs as well as number of samples taken for every input every line cycle temperature a...

Страница 48: ...ted setting Press the ENTER pushbutton or ESCAPE pushbutton to exit TEST SPEED Values between 001 and 023 can be selected A smaller number indicates a faster speed for the test pattern SCREEN TEST Whe...

Страница 49: ...tart of frame errors SOF and number of end of frame errors EOF This display is view only Press the ENTER pushbutton or the ESCAPE pushbutton to exit 4 6 6 6 3 Ethernet Port Statistics This display sho...

Страница 50: ...incorrectly displayed depending on the type of diagnostic failure being experienced SHORT YEL ON Field inputs that were ON for at least 100 milliseconds at the time of the fault FLASHING The Yellow fi...

Страница 51: ...ontroller Unit LOC FLASH The monitor is configured to operate with the Disable Local Flash feature enabled RED FAIL The Red Enable input Connector B Pin a is below 70VAC The LOAD SWITCH Flash bit is s...

Страница 52: ...to enter the mode To enter the diagnostic display mode press and hold the front panel RESET pushbutton for more than 1 5 seconds but less than three seconds The buzzer will emit a single chirp when 1...

Страница 53: ...for the current configuration The right display is the last two digits of the CRC for the current configuration There is lower case h added to the end of the CRC to show that it is displayed in hexade...

Страница 54: ...feature 6 Disable Local Flash feature 7 Per Channel Red Enable Co Channel feature 8 24V 2 To 12VDC feature 9 through 14 are reserved for future features 15 Flashing Yellow Arrow Monitoring feature 16...

Страница 55: ...l Displays The left display is the ID Display C1 The right display is the Data Display On the Data Display FLASHING The channel with the flashing R Y and G is the channel whose Co Channel Childs are b...

Страница 56: ...e selection between Program Card and MMU Then press the ENTER pushbutton or press and hold the RESET pushbutton for 5 seconds There will be five quick confirmation beeps to confirm that the selection...

Страница 57: ...A E web site www renoae com 3 Connect the monitor to the computer through the COMM PORT or ETHERNET 10 100 port on the MMU 1600GE 4 Start the RaeComM program 5 Ensure that the RaeComM software can co...

Страница 58: ...unctions Clear Logs Clear All Logs Logging Thresholds View Prior Faults Log View Signal Sequence Log Clear Date Time Log Clear AC Line Log Clear Resets Log Clear Configurations Log Clear Prior Faults...

Отзывы: