background image

 

Model MMU-1600G Series Op Man - Ver 1.07.23 - Rev 20151026DL 

Page 40 of 58 

 

Use the left (◄) or right (►) pushbutton to select the field to change.  Use the up (▲) or down (▼) pushbutton to scroll the 
viewing window to the other channels.  Use the 

ENTER

 pushbutton to toggle the setting.  Press the 

ESCAPE

 pushbutton to 

exit. 

FYA  ENABLE

 – When this feature is enabled the monitor disables the Co-Channel feature and uses the channel  mapping 

table for Flashing Yellow Arrow channel programming instead.  The factory default for this feature is 

NO

.

 

FYA  IGNORE  YEL  CONFLICT

  –  When  this  feature  is  enabled  the  monitor  will  ignore  a  Yellow  to  Yellow  conflict 

between  the  channel  with  the  protected  left  turn  displays  and  the  opposing  through  channel  when  terminating  a  Flashing 
Yellow Arrow.  Most FYA implementations will need to use this feature.  The factory default for this feature is 

NO

.

 

FYA DRIVER IS YEL

 – When this feature is enabled the monitor will use the Yellow input of the FYA channel as the input 

driving  the  FYA  display.    When  this  feature  is  disabled  the  monitor  will  use  the  Green  input  as  the  driver  for  the  FYA 
display.  The factory default for this feature is 

NO

 (Green input).

 

CHANNEL  1-16  FLASHING  YELLOW  ARROW  MAPPINGS

  –  The  number  on  the  left  indicates  the  channel  that  the 

channel mappings to the right will apply to.  The only channels that should have mappings are the ones that are protected left 
turn displays.  There should be two mappings for each channel that is the protect display of an FYA head.  The first is the 
permissive  channel.    This  is  the  channel  that  the  Flashing  Yellow  Arrow  is  connected  to.    The  other  is  the  opposing 
conflicting channel that  is active  while in the permissive portion of the left turn  movement.  The program card should  be 
programmed with the FYA channel as permissive with the protected left turn channel.  When correct, one mapping will show 
an 

R

  indicating  the  conflicting  channel  and  the  other  will  show  a 

Y

  or 

G

  indicating  which  input  for  that  channel  will  be 

monitored as the FYA display.

 

The per channel mappings will be active only if the FYA Enable setting is set to 

YES

.  The factory default for the channel 

settings of this feature is all channels unmapped. 

4.6.2.1.7.6 

Co-Channel Child Settings 

The Co-Channel Childs feature allows the user to modify the Red Fail test for each channel to include the Green, Yellow, 
and/or Walk displays from other channels.  This allows for Red Fail monitoring of heads with more than 3 sections.  This 
feature is mutually exclusive with FYA Enable.  If FYA Enable is set to 

YES

, you will not be able to access this screen.  You 

will need to go the FYA Left Turns display and set the FYA Enable to 

NO

 to view this display.  See Section 

2.6.2

 for more 

detailed information on Co-Channel Monitoring. 

Use the left (◄) or right (►) pushbutton to select the field to change.  Use the up (▲) or down (▼) pushbutton to scroll the 
viewing window to the other channels.  Use the 

ENTER

 pushbutton to toggle the setting.  Press the 

ESCAPE

 pushbutton to 

exit. 

CO-CHAN  /  PER  CHAN  RED  EN

  –  When  this  feature  is  enabled  the  monitor  will  modify  how  a  Red  Fail  test  is 

performed.    For  each  parent  channel  (row)  the  Green  (and  the  Walk  if  in  Type  12  mode)  and  optionally  the  Yellow  of 
additional channels (childs) may be included in the Red Fail test for that channel.  The factory default for this feature is 

NO

Enabling this feature also enables the Per Channel Red Enable feature.  The Per Channel Red Enable feature allows the user 
to  only  perform  Red  Fail  and  Field  Check  monitoring  for  channels  that  have  been  enabled  for  this  feature  when  the  Red 
Enable input is active. 

CO-CHAN INCLUDES  YEL

 – When this feature is enabled the monitor will include the yellow of the child channels as 

well as the green (and the Walk if in Type 12 mode).  The factory default for this feature is 

NO

CHANNEL 1-16 CO-CHANNEL CHILDS SETTINGS

 – The numbers at the left side of the screen correspond to parent 

channels.  The small numbers  across the top  of the screen  correspond to child channels.  Enabled is  indicated by a 

Y

 and 

disabled is indicated by a dash

 

(

).  The per channel settings will be active only if the Co-Chan / Per Chan Red En setting is 

set to 

YES

.  The factory default for the channel settings of this feature is all channels have no childs enabled. 

4.6.2.1.7.7 

Threshold Settings 

Use the up (▲) or down (▼) pushbutton to navigate between the settings.  Use the 

ENTER

 pushbutton to toggle the setting.  

Press the 

ESCAPE

 pushbutton to exit. 

LED  THRESHOLDS

  –  When  this  feature  is  enabled  the  monitor  will  use  more  restrictive  AC  voltage  thresholds  for 

determining the ON and OFF state of field indications.  See Section 

2.6.4

 

for more information.  The factory default for this 

feature is 

NO

24V-2 TO 12VDC

 – When this feature is enabled the +24V Monitor II input thresholds will be modified to m12 

VDC.  The new voltage threshold will be 11.5 VDC and above, sensed as valid; 10.75 VDC and below, sensed as invalid.  
Voltages between these thresholds may be sensed as valid or invalid.  See Section 

2.6.7

 for more information.  The factory 

default for this feature is 

NO

Содержание MMU-1600G Series

Страница 1: ...NO A E Reno A E 4655 Aircenter Circle Reno Nevada 89502 USA Telephone 775 826 2020 Facsimile 775 826 9191 Internet www renoae com E mail contact renoae com NEMA TS 2 20 NEMA TS 2 2003 Malfunction Mana...

Страница 2: ...nagement Unit was designed built inspected and tested to ensure its proper operation It is Reno A E s recommendation that each Malfunction Management Unit be tested at least annually to ensure complia...

Страница 3: ...2 4 2 Minimum Flashing Indication 11 2 4 3 Reset 11 2 4 4 Type 16 Only Mode 11 2 4 5 COM Port 11 2 4 6 Ethernet Port 11 2 4 7 Temperature Sensor 12 2 4 8 Real Time Clock 12 2 4 9 Up Time Accumulator...

Страница 4: ...Upgrade Pending 35 4 5 Voltage Displays 35 4 6 Main Menu 35 4 6 1 Identification Menu 36 4 6 1 1 User Unit Information 36 4 6 1 2 Factory Unit Information 36 4 6 1 3 Ethernet Settings 36 4 6 2 Configu...

Страница 5: ...atus Menu 47 4 6 5 1 Channels 1 6 47 4 6 5 2 Channels 7 12 47 4 6 5 3 Channels 13 16 47 4 6 5 4 Other AC and Miscellaneous Inputs 47 4 6 5 5 DC Inputs 47 4 6 6 Diagnostic Info 48 4 6 6 1 LED Test Sett...

Страница 6: ...Walk inputs associated with a channel shall be considered as that channel being active The signal monitor portion of the monitor is also capable of checking for the absence of any required signal vol...

Страница 7: ...to the chassis of the unit This input is not connected to Logic Ground or AC Neutral within the unit Typical Connection Cabinet Earth Ground 2 1 4 Field Terminals Reds Yellows Greens and Walks The fi...

Страница 8: ...ut Type Select input 24V Monitor Inhibit input Local Flash Status input and Port 1 Disable input as well as the Port 1 SDLC communications signals This termination Connector A Pin T is not connected t...

Страница 9: ...binet Interlock The monitor has two terminals internally connected to indicate the presence of the unit to external circuitry These terminals are identified as Cabinet Interlock A Connector A Pin CC a...

Страница 10: ...een pairs of holes for Minimum Yellow Change Disable programming jumpers The sixteen jumper hole pairs are logically labeled for easy identification of the channel numbers A soldered wire jumper in a...

Страница 11: ...ew reset input to the monitor Activation of either reset will cause all of the front panel LEDs to turn on for 300 milliseconds The only intended purpose of the reset input is to facilitate automated...

Страница 12: ...rational SDLC bus any time setting entered via the front panel will be overwritten by the Controller Time setting If it is necessary to change the Real Time Clock setting in a monitor that is being us...

Страница 13: ...transfers the Output relay contacts to the fault condition continuity between the Normally Open and Common contacts illuminates the CONFLICT indicator on the front panel and sets the Conflict bit bit...

Страница 14: ...ow Arrow Left Turns When Flashing Yellow Arrow FYA Left Turns are enabled and a Channel has an FYA setting of G for one of its child channels then the Green of the child channel will be included in th...

Страница 15: ...l has a Green and a Yellow display active a dual indication timer is started If one of the indications turns off the dual indication timer is stopped it is not cleared and a single indication timer is...

Страница 16: ...ft Turns When Flashing Yellow Arrow FYA Left Turns are enabled and a channel has an FYA setting with a setting of G or Y for one of its child channels then the Yellow of the channel will be used for t...

Страница 17: ...f this fault Modifying Inputs Red Enable All field check testing will be disabled when this input is below 70VRMS Port 1 Disable All field check testing will be disabled when this input is below 8VDC...

Страница 18: ...est Preformed A voltage greater than 22VDC applied to the 24 Volt Monitor II input is recognized as adequate for proper operation A voltage of less than 18VDC is recognized as inadequate for proper op...

Страница 19: ...contacts to the fault condition continuity between the Normally Open and Common contacts illuminates the LOC FLASH indicator on the front panel and sets the Local Flash bit bit 79 of the Type 129 Fra...

Страница 20: ...cal Use This feature is used to provide additional fault checking for Flashing Don t Walk displays Without this feature a flashing Red input is never checked for conflicts 2 6 2 Co Channel Monitoring...

Страница 21: ...re the unused Green or Yellow of that channel for conflict tests Red Fail Normal red fail testing ensures that at least one display is active for a channel With this feature active any channel with a...

Страница 22: ...elow 15VRMS Reds are ON when their voltage is above 70VRMS and OFF when below 50VRMS With LED thresholds the monitor senses Greens Yellows Reds and Walks as ON when their voltage is above 25VRMS and O...

Страница 23: ...ration is allowed Typical Use This feature is useful when it is desirable to ignore a command to begin flash operation of the intersection This may come from a Time Clock or an output of the Controlle...

Страница 24: ...g The AC Line Log records the 50 most recent changes in AC line status Data recorded Date Time Stamp Event Type Power Up Reset Low Voltage Low Voltage Recovery Shutdown Low Voltage Alarm Low Voltage A...

Страница 25: ...ype 129 Frame being set to 1 NOTE Port 1 communications may not be possible during certain diagnostic failures 2 8 1 Memory The monitor verifies all memory elements on power up or upon reset of a Diag...

Страница 26: ...DSP Timeout 6 0020h The DSP did not respond to a request for data in the required amount of time Ethernet Port Error 7 0040h The interface hardware for the Ethernet port is not functioning properly D...

Страница 27: ...metal shell D subminiature receptacle with gold plated female contacts and nuts for retaining screws ETHERNET CONNECTOR High speed 10Base T 100Base TX RJ 45 network jack optional 3 2 ELECTRICAL POWER...

Страница 28: ...TIMING FUNCTIONS START DELAY 2 0 sec 0 5 sec MINIMUM FLASH 6 to 16 sec 1 sec PORT 1 FAIL Typical 300 msec FIELD CHECK FAIL Typical 1000 msec CONFLICT No Fault 200 msec Detect 450 msec Typical 300 mse...

Страница 29: ...2 Only I Channel 10 Walk I b Channel 10 Yellow I Channel 10 Yellow I c Channel 9 Yellow I Channel 9 Yellow I d Channel 8 Yellow I Channel 8 Yellow I e Channel 7 Yellow I Channel 7 Yellow I f Channel 6...

Страница 30: ...ype 16 Only I U Start Delay Relay N C Open During Start Delay O Start Delay Relay N C Open During Start Delay O V Channel 10 Red I Channel 10 Red I W Channel 14 Red I Channel 14 Red Type 16 Only I X C...

Страница 31: ...served Reserved 20 5 9 5 10 5 11 20 Reserved Reserved Reserved 21 5 12 5 13 5 14 21 Minimum Flash Minimum Flash Minimum Flash 22 5 15 5 16 6 7 22 Minimum Flash 24V Latch CVM Latch 23 6 8 6 9 6 10 23 R...

Страница 32: ...wer is low Type 12 LED ON Type 12 Mode OFF Type 16 Mode Blip Type 16 Only Receive Transmit Receive ON A valid SDLC frame addressed to the monitor was received Transmit ON A SDLC frame was transmitted...

Страница 33: ...Prior Date Time Functions Clear Logs Clear All Logs Logging Thresholds View Prior Faults Log View Signal Sequence Log Clear Date Time Log Clear AC Line Log Clear Resets Log Clear Configurations Log Cl...

Страница 34: ...button will display the Configuration Shortcuts menu Right Pushbutton The pushbutton labeled is used to navigate through menu selections or settings being viewed If the setting being viewed can be ch...

Страница 35: ...toring Menu and select Save Changes 4 4 4 Upgrade Pending When new firmware has been downloaded in to the monitor the Run Time display will indicate that there is a pending upgrade and that you need t...

Страница 36: ...d is typically used to store the intersection that the monitor is installed at example VIRGINIA AVE LONGLEY AVE UNIT ID This text field is four 4 characters long The user can edit this field This fiel...

Страница 37: ...s monitor to the factory defaults WIZARD Access the configuration wizard that can be used to automatically configure most settings in the monitor 4 6 2 1 1 Start Configuration Before a change can be m...

Страница 38: ...an monitoring settings FYA LEFT TURNS View and or modify the Flashing Yellow Arrow Left Turn settings CO CHANNELS View and or modify the Co Channel settings THRESHOLDS View and or modify threshold set...

Страница 39: ...ushbutton to toggle the setting Press the ESCAPE pushbutton to exit See Section 2 6 5 for more detailed information on Per Channel Red Enables PER CHAN RED EN CO CHAN When this feature is enabled the...

Страница 40: ...f heads with more than 3 sections This feature is mutually exclusive with FYA Enable If FYA Enable is set to YES you will not be able to access this screen You will need to go the FYA Left Turns displ...

Страница 41: ...atus of an optional external watchdog output from a Controller Unit or other external cabinet device See Section 2 5 13 for more information The factory default for this feature is NO TYPE 16 ONLY Whe...

Страница 42: ...tored O Overlap or Other Used channels not covered by the above three options Unused 4 6 2 1 10 3 Left Turn Configurations LEFT TURN TYPE Select the type of left turn You will get this screen for ever...

Страница 43: ...ts given to the wizard 4 6 2 1 10 6 Almost Done If there were no warning or you ignored all warnings you will get the Almost Done screen Pressing ENTER here will create a new configuration based on th...

Страница 44: ...CONFIGURATIONS LOG Access the View Configurations Log menu VIEW PRIOR FAULTS LOG View the Prior Faults log VIEW SIGNAL SEQUENCE LOG View the Signal Sequence log 4 6 3 1 1 View Date Time Log The monito...

Страница 45: ...re each of the previous nine 9 monitor configurations stored in the Configurations Log to the current monitor configuration Date and Time the total number of Different Features a list of the Different...

Страница 46: ...CONFIGURATIONS LOG Clear the Configurations log CLEAR PRIOR FAULTS LOG Clear the Prior Faults log CLEAR SIGNAL SEQUENCE LOG Clear the Signal Sequence log For each of these screens use the arrow pushb...

Страница 47: ...eld inputs for channels 13 through 16 OTHER AC MISC INPUTS View the real time voltages on the AC and Red Enable inputs as well as number of samples taken for every input every line cycle temperature a...

Страница 48: ...ted setting Press the ENTER pushbutton or ESCAPE pushbutton to exit TEST SPEED Values between 001 and 023 can be selected A smaller number indicates a faster speed for the test pattern SCREEN TEST Whe...

Страница 49: ...tart of frame errors SOF and number of end of frame errors EOF This display is view only Press the ENTER pushbutton or the ESCAPE pushbutton to exit 4 6 6 6 3 Ethernet Port Statistics This display sho...

Страница 50: ...incorrectly displayed depending on the type of diagnostic failure being experienced SHORT YEL ON Field inputs that were ON for at least 100 milliseconds at the time of the fault FLASHING The Yellow fi...

Страница 51: ...ontroller Unit LOC FLASH The monitor is configured to operate with the Disable Local Flash feature enabled RED FAIL The Red Enable input Connector B Pin a is below 70VAC The LOAD SWITCH Flash bit is s...

Страница 52: ...to enter the mode To enter the diagnostic display mode press and hold the front panel RESET pushbutton for more than 1 5 seconds but less than three seconds The buzzer will emit a single chirp when 1...

Страница 53: ...for the current configuration The right display is the last two digits of the CRC for the current configuration There is lower case h added to the end of the CRC to show that it is displayed in hexade...

Страница 54: ...feature 6 Disable Local Flash feature 7 Per Channel Red Enable Co Channel feature 8 24V 2 To 12VDC feature 9 through 14 are reserved for future features 15 Flashing Yellow Arrow Monitoring feature 16...

Страница 55: ...l Displays The left display is the ID Display C1 The right display is the Data Display On the Data Display FLASHING The channel with the flashing R Y and G is the channel whose Co Channel Childs are b...

Страница 56: ...e selection between Program Card and MMU Then press the ENTER pushbutton or press and hold the RESET pushbutton for 5 seconds There will be five quick confirmation beeps to confirm that the selection...

Страница 57: ...A E web site www renoae com 3 Connect the monitor to the computer through the COMM PORT or ETHERNET 10 100 port on the MMU 1600GE 4 Start the RaeComM program 5 Ensure that the RaeComM software can co...

Страница 58: ...unctions Clear Logs Clear All Logs Logging Thresholds View Prior Faults Log View Signal Sequence Log Clear Date Time Log Clear AC Line Log Clear Resets Log Clear Configurations Log Clear Prior Faults...

Отзывы: