DN-Series Integrated Programmable Controls
DOAS
SYSTEM MONITORING
If you need to set the timing values, you can do that here.
13.3.3 Modbus RTU Settings
First, set the address, baud rate, stop bits and parity.
Then set the timeout parameter if needed.
13.7.4 Modbus RTU Wiring
The Modbus RTU network is wired into the four-pin connector named J3 Disp. In the upper
left-hand corner of the controller. This is also used for a RUT display so the two cannot be
used at the same time. For Modbus RTU, use the plus (+) and minus (-), as well as the GND for
reference if desired.
DO NOT use the +Vterm terminal. If you happen to plus a three-pin block in here and use the
wrong three pins you might damage the port.