DN-Series Integrated Programmable Controls
DOAS
SYSTEM MONITORING
TYPE
INSTANCE
VARIABLE NAME
DESCRIPTION
VALUE
RANGE
READ/WRITE
(RET)
Analog Input
26
SF_Command.Val
Supply Fan Command
(actual)
%
Read_NoWrite
Analog Input
27
EF_Command.Val
Exhaust Fan Command
(actual)
%
Read_NoWrite
Analog Input
28
CO2_VOC_Level.Val
CO2 or VOC Level
PPM
Read_NoWrite
Analog Input
29
Cooling_LAT.Val
Cooling Coil Leaving Air
Temperature
F
Read_NoWrite
Analog Input
31
Duct_Press.Val
Duct Pressure
iwc
Read_NoWrite
Analog Input
32
CA_Temp.Val
CA Temperature (after
tempering)
F
Read_NoWrite
Analog Input
33
Cooling_Command.Val
Cooling Command
%
Read_NoWrite
Analog Input
34
Heating_Command.Val
Heating Command from
Program
%
Read_NoWrite
Analog Input
59
Bypass_Command.Val
Bypass Damper
Command
%
Read_NoWrite
Analog Input
62
HGRH_Command.Val
HGRH Valve Command
%
Read_NoWrite
Analog Value
34
HeatingCommand_BMS Heating Command from
BMS
%
Read_Writeable
Analog Value
35
RA_Flt_AlarmHigh
RA Filter Alarm Level
iwc
Read_Writeable (X)
Analog Value
36
OA_Flt_AlarmHigh
OA Filter Alarm Level
iwc
Read_Writeable (X)
Analog Value
37
SF_ConstSpeedSetP.Val SF Const Speed Setpoint
%
Read_Writeable (X)
Analog Value
38
SF_FlowControlSetP.Val SF Flow Control Setpoint
CFM
Read_Writeable (X)
Analog Value
39
SF_DuctStaticSetP.Val
SF Duct Static Pressure
Setpoint
iwc
Read_Writeable (X)
Analog Value
41
SF_CO2_VOCSetP.Val
SF CO2 or VOC Setpoint
PPM
Read_Writeable (X)
Analog Value
43
EF_ConstSpeedSetP.Val EF Constant Speed
Setpoint
%
Read_Writeable (X)
Analog Value
44
EF_FlowControlSetP.Val EF Flow Control Setpoint
CFM
Read_Writeable (X)
Analog Value
45
EF_SF_TrackingSetP.Val EF SF Tracking Setpoint
%
Read_Writeable (X)
Analog Value
46
EF_ReturnStaticSetP.
Val
EF Return Static Setpoint iwc
Read_Writeable (X)
Analog Value
47
CoolLockoutTemp
OA Cooling Lockout
Temperature
F
Read_Writeable (X)
Analog Value
48
HeatLockoutTemp
OA Heating Lockout
Temperature
F
Read_Writeable (X)
Analog Value
50
Econ_Temp_Diff
Economizer Temperature
Differential
F
Read_Writeable (X)
Analog Value
51
Economizer.Econ_Low_
OA_Temp_Limit
Economizer Low OA
Temp Limit
F
Read_Writeable (X)
Analog Value
52
Economizer.Econ_
Hysteresis
Economizer Hysteresis
Btu/lb
Read_Writeable (X)
Analog Value
53
BMS_CO2_VOC_
Reading
BMS CO2 or VOC Reading
(in lieu of attached
sensor)
PPM
Read_Writeable