1.800.627.4499
DN-Series Integrated Programmable Controls
DOAS
76
I/O AND UNIT WIRING
9.3.4 Analog Outputs
Outputs in Grey are optional, and field-installed. Heating and cooling may be factory-installed or
field-installed, depending upon the unit.
OUTPUT
TYPE
OUTPUT
TERMINALS
INTERMEDIATE
TERMINALS
CONTROLLER
TERMINALS
SF Signal
0–10VDC
01-6-D
Y1 (Main)
01-2-D
GND
EF Signal
0–10VDC
01-4-D
Y2 (Main)
01-2-D
GND
Bypass Command
0–10VDC
X3-23 (Black)
U4 (EXP)
X3-27
GND
HGRH Command
0–10VDC
X3-28 (Red)
U8 (EXP)
X4-31
Sensor COM
Cooling Command
0–10VDC
X3-29 (Black)
U9 (EXP)
X4-31
Sensor COM
Heating
Command
0–10VDC
(See below for
gas module)
X3-30 (White)
U10 (EXP)
X4-31
Sensor COM
9.3.4.1 Factory-Installed Gas Module Wiring—Analog
For gas modules with 10:1 turndown, see this diagram:
Gas Module
X3-30
X3-31
T12(+)
T13 (-)
For gas modules with 5:1 turndown, see this diagram:
Gas Module
X3-30
X3-31
T11(+)
T10 (-)