DN-Series Integrated Programmable Controls
DOAS
150
REFERENCE
16.5.1.4 RenewAire Parameter Settings
PARAMETER
NAME/SELECTION
ABB N831
OR ACS320 HVAC
DEFAULT
SETTINGS AS SHIPPED BY
US
COMMENTS
1611
PARAMETER VIEW
2=SHORT VIEW ACS320
3=LONG VIEW ACS355
3=LONG VIEW
Technician needs to set to LONG VIEW
in order to edit some parameters in
ACS320 VFDs
1103
REF1 SEL
1=AI1
1=AI1
Leave at Default value for CC units
1104
REF1 MIN
0.0 Hz
15 Hz
Added parameter for CC units
1105
REF1 MAX
60.0 Hz
60.0 HE, 90.0 LE units,
120.0 DN units
Added parameter for CC units
1301
MINIMUM AI1
20.0%
0%
Added parameter for CC units
1302
MAXIMUM AI1
100.0%
100.0%
Leave at Default value for CC units
1401
RELAY OUTPUT 1
1=READY
2=RUN
1601
RUN ENABLE
0=NOT SEL
1=DI1
Added parameter for CC units
1608
START ENABLE 1
4=DI4
4=DI4
Leave at Default value for CC units
2003*
MAX CURRENT
1.8*I2N
Typically 125% FLA for
>=1.15 SF Motor (*see
exceptions)
CRITICAL PARAMETER. This provides
motor protection!
2007
MINIMUM FREQ
0.0 Hz
15.0 Hz
2008
MAXIMUM FREQ
60.0 Hz
60.0 HE, 90.0 LE units,
120.0 DN units
2101
START FUNCTION
1=AUTO
6=SCAN START
ACS320 arrives with P2101 default at
e6=SCAN START but ACS320 manual
says default is 1=AUTO
2607
SWITCHING
FREQUENCY
2=ON (LOAD)
1=ON
Set to match ACS320 Default
3007**
MOT LOAD CURVE
100%
Typically 98% for >=1.15 SF
Motor (**see exceptions)
CRITICAL PARAMETER. This provides
motor protection!
3401
SIGNAL 1 PARAM
103=OUTPUT
FREQUENCY
101=SPEED AND DIR
Changing P3401 will also change
P3405 to RPM and P3407 to 30000
rpm listed in CHANGED PARAMETERS
3418
OUTPUT 3 DSP
FORM
9=DIRECT
8=BAR METER
Added parameter for CC units
3419
OUTPUT 3 DSP UNIT 11=mA
4=%
Added parameter for CC units
3421
0UTPUT 3 MAX
200%
100%
Added parameter for CC units
9802
COMMUNICATION
PROTOCOL
SELECTION
5=BACnet
0=NOT SELECTED
Set to match ACS320 Default
9901
LANGUAGE
ENGLISH
ENGLISH (AM)
9905
MOTOR NOM VOLT
Varies
Equal to Motor Nameplate
Volts
When unit is marked 208–230V, set
this value at 208V.
9906
MOTOR NOM CURR
Varies
Equal to Motor FLA (*per unit
nameplate, see exceptions)
When unit is marked 208–230V, set
this value at the FLA corresponding to
208V.
9908
MOTOR NOM SPEED Varies
Equal to motor nominal RPM.
See separate document.
9909
MOTOR NOM
POWER
Varies
Equal to motor nameplate HP
(*see exceptions)