DN-Series Integrated Programmable Controls
DOAS
22
UNIT CONFIGURATION
4.1.4 Scheduler
Enable the scheduler, if desired. If you enable the scheduler, it will have to be set for “ON” for
the unit to run along with all other “ON” conditions.
u
Enable the scheduler by setting to YES.
u
Set the schedule for each day. You can use the copy feature to copy days. Save data
after each.
u
Set vacation periods.
u
Set Special Days.
4.2 VERIFY UNIT CONFIGURATION
It is important to verify the configuration as the settings on these screens will also determine
which screens show up in the user settings screens.
4.2.1 Main Unit Configuration
Depending upon how the unit was ordered, set the following settings:
u
Enable Heat, if applicable.
u
Enable Cooling, if applicable.
u
Enable HGRH (Hot Gas Reheat), if coil present.
u
Set heating and cooling types here, if desired. Or set them in the
Control Settings
later.
u
Enable frost control, if desired.
u
If recirculation dampers were ordered with unit, enable here.