DN-Series Integrated Programmable Controls
DOAS
OVERVIEW
1.5 SENSOR LOCATIONS
OVERFLOW
SWITCH
MONITORS
CONDENSATE
LEVEL. ATTACHED
TO CONDENSATE
PAN (OPTIONAL)
EA STREAM
TEMPERATURE
SENSOR
(MOUNTED ON
AIR INLET CONE)
EA FAN AND SA
FAN CURRENT
SWITCHES
(MOUNTED ON
LOW-VOLTAGE
SIDE OF E-BOX
EA FAN
FLOW RATE
OA FILTER PRESSURE
RA FILTER PRESSURE
RA
TEMPERATURE
AND HUMIDITY
OA
TEMPERATURE
AND HUMIDITY
SA STREAM TEMPERATURE
SENSOR (MOUNTED ON
AIR INLET CONE WHEN THE
SA FAN IS POSITIONED
UPSTREAM OF THE COOLING
COIL. WHEN THE SA FAN IS
POSITIONED DOWNSTREAM
OF THE COOLING COIL, THE
SENSOR IS POSITIONED ON
THE CORE LEAVING SIDE OF
THE AIRSTREAM)
SA FAN FLOW RATE
COOLING COIL
LEAVING AIR
TEMPERATURE
SENSOR (ON
LEAVING SIDE OF
COOLING COIL WHEN
HGRH PRESENT)
CA TEMPERATURE
SENSOR (ON
LEAVING SIDE
OF THE HEATING
MODULE)
MAY BE LOCATED
IN DOWNSTREAM
DUCTWORK
NOTE: Not shown
here are the Smoke
Detector, CO2,
IAQ, Duct Pressure
Sensor, Room Temperature
and Humidity Sensor, and
Motion Detector. These
items are all accessories
and are field-installed.
FIGURE 1.5.0 SENSOR LOCATIONS IN DN-SERIES UNITS