45
reset heat (Yes/No)
Measured heat values are reset (all statistics, from hourly to total
values).
reset flow (Yes/No)
Measured values of flow rate and fluid volume passed through are
reset (all statistics, from hourly to total values).
S 2.14 – Total statistics
Statistics of sources and all pumps operation and of solar tanks heating, in HH:MM format.
S 2.15 – Control type
Warning:
Changing the number of hydraulic variant will cause most settings to be
overwritten. Always change the hydraulic variant first, before starting to
adjust other values.
Here the setting of the hydraulic variant is done, following the document: IR12 Intelligent
Controller - typical designs of hydraulic variants that is enclosed. The document can be also
downloaded from the service level of the controller website.
After you select the Hydraulic variant number (press OK in the display shown, set the desired
number using up/down arrows in the range 1 to 34 and confirm by pressing OK), the control
type will be set automatically as well as all the other variables concerning the selected
variant.
For the control type 1, the heating return valve and temperature sensor are connected and
Zone 1 is unmixed. For the control type 2, Zone 1 is mixed (i.e. a zone mixing valve is
installed instead of a heating return valve) and a Zone 1 heating water temperature sensor is
connected instead of a heating return temperature sensor. In that case the system features
no heating return valve.
Hydraulic v. (1 to 33)
Choosing control manner.