T setback setback temperature. Hot water storage tank gets heated up to this temperature if the
program is set to “Setback“ at the moment.
T from ThS hot water storage tank is heated to this temperature (at DHWL sensor) from this
function disregarded of time schedules and comfort/setback temperatures selected.
zone on
DHW zone heated by heat pump switched on by User.
Anti Legionella:
Anti-Legionella function helps “disinfect” hot water storage tanks, namely it kills Legionella
bacteria.
When this function is ON, the hot water storage tank heats up to 65°C once in a week, at a
preset time on a preset day. Heating is switched off either when this temperature is reached,
or after two hours of heating disregarded of the temperature.
on
turns Anti Legionella function on.
day (weekday: mo-su)
day when heating up starts.
hour
hour when heating up starts.
2.3 DHW recirculation
Here DHW recirculation is enabled and the time schedule of the pump set. When
recirculation is on, it is performed following the time schedule set for each day. The time