an extra option (fromZ1) and in such a case the data from RC21 unit wired to
zone 1 are valid for zone 2.
no room sens.recalc. DTheat./room (°C) Temperature drop setting between heating water and
room temperature. E.g. the value 3 means that a desired change in room
temperature by 1°C needs a heating water temperature change by some 3°C.
This parameter is applied for operation without any room sensors.
smooth change time day/night (min)
Time adjustment of how many minutes the controller
will need to change from comfort to setback temperature during daily
scheduled transition between day and night modes and vice versa.
The influence of room temperature on heating water:
max. increase (°C) Setting the max. permitted positive influence on the OTC curve calculated by
the Controller based on the difference between the real and desired
temperatures in zone (see fig. below).
max. decrease (°C) Setting the max. permitted negative influence on the OTC curve calculated by
the Controller based on the difference between the real and desired
temperatures in zone (see fig. below).