diff. on (°C)
Setting the difference between boiler return temperature and that
demanded by a heating system, for source 2 to be switched on.
diff. off (°C)
Setting the difference between boiler return temperature and that
demanded by a heating system, for source 2 to be switched off.
delay (min)
Setting the delay in boiler start after the demand based on
temperature difference appeared.
out block (°C)
Setting the outdoor temperature limit above which the Source 2 will be
blocked.
Ripple c. (yes/no) Setting Source 2 control via Ripple control.
sensor to turn on (sensor list)
Decisive sensor to turn the source on.
sensor to turn off (sensor list)
Decisive sensor to turn the source off.
S 2.6 – Setting service parameters of a modulated (0-10V) heat source
Control sensor for the source can be selected on the second settings screen.
source 0-10V (yes/no)
Switching on a 0-10V signal controlled heat souce on service level.
output (power/temp.)
Setting the type of output signal. With power selected, the 0-10V
signal is in direct relationship to the desired source output (in the
range adjustable on the respective adjustment page). With temp.