![Regulus IR 12 Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/regulus/ir-12/ir-12_user-manual_1434395024.webp)
24
uni. output
universal output 1 (controller universal terminal)
uni. output 2
universal output 2 (controller second universal terminal)
sms
switching on SMS function (adjustable from user interface)
heat
settings for heat and flowrate measurements
statistics
statistics for some parameters
control type
control type choice (mixed zone 1/heating return valve)
test
controller outputs test
module UNI
universal CIB module configuration
CIB address
HW addresses for additional CIB modules
IP address
set IP address, subnet mask, default gateway and DNS server
RegulusRoute
settings to TecoRoute service
S 2.1 – Heating zones setting (1,2)
Settings are identical for both heating zones.
zone (on/off)
Turning zone on/off from service level. In a zone turned off this way the frost
protection is disabled.
max.t to zone (°C) Setting max. heating water temperature to zone. Temperature calculated by
the controller shall not be higher than this value. Max. temperature to zone 2
cannot be higher than max. temperature to zone 1; when attempted to set
higher, it will be adjusted to the max. temperature of zone 1!!
min.t to zone (°C) Setting min. heating water temperature to zone. Temperature calculated by
the controller shall not be lower than this value.
room sensor
Choose whether a Pt1000 room sensor (Pt) used in the zone, or RC21 room
unit (RC21) or no room sensor (none). Or you can choose thermostat (therm)
for switching between comfort and setback temperature. For zone 2 there is