Manual Corrigo E Ventilation, revision M
Chapter 16
Configuration
73
Chapter 16 Configuration
Start by logging on at System level. See chapter 8.
Move the marker using the DOWN and UP buttons until it is opposite the menu
Configuration
and
press RIGHT.
The configuration main menu is shown (different menus are visible depending on the configured
inputs and outputs).
Inputs/Outputs
Control function
Fan control
Extra control unit
Extra sequence Y4
Heating
Exchanger
Cooling
Pump control
Free cooling
Support control
CO2/VOC control
Fire function
Humidity control
Exchanger de-icing
Cooling recovery
Enthalpy control
Min lim. dampers
External setpoint
Run ind/Motor prot.
Actuator type
Actuator run time
Step controllers
Recirculation
Alarm settings
Communication
Other parameters System
16.1 Inputs and outputs
Analogue inputs
Digital inputs
Universal inputs
Analogue outputs
Digital outputs
General
Free configuration
Any control signal can be bound to any input/output, the only restriction being that digital signals
cannot be bound to analogue inputs and vice versa. It is up to the user doing the binding to make
sure that activated functions are bound to appropriate signals.
Delivery setting
On delivery all the physical inputs and outputs have already been bound to a signal.
The delivery settings are suggestions only and can easily be changed.