Manual Corrigo E Ventilation, revision M
Chapter 13
Time settings
63
Chapter 13 Time settings
General
Corrigo has a year-base clock function. This means that a week-schedule with holiday periods for a
full year can be set. The clock has an automatic summer- winter-time changeover.
Individual schedules for each week-day plus a separate holiday setting. Up to 24 individual holiday
periods can be configured. A holiday period can be anything from one day up to 365 days. Holiday
schedules take precedence over other schedules.
Each day has up to two individual running periods. For two-speed fans and pressure controlled fans
there are daily individual schedules for normal speed and reduced speed, each with up to two
running periods.
Up to 5 digital outputs can be used as timer controlled outputs. Each with individual week-
schedules with two activation periods per day. These outputs can be used to control lighting,
doorlocks etc.
Time/Date
Timer Normal speed
Timer Reduced speed
Extended running
Timer output 1
Timer output 2
Timer output 3
Timer output 4
Timer output 5
Holidays
13.1 Time / Date
This menu shows and permits the setting of time and date.
Time is shown in 24 hour format.
Date is shown in the format YY:MM:DD
Time: 18:21
Date: 04-08-04
Weekday: Wednesday
13.2 Timer Normal speed
There are 8 separate setting menus, one for each weekday and one extra for holidays.
Holiday schedules take precedence over other schedules.
For 24 hour running, set a period to 0:00 – 24:00.
To disable a period, set it to 0:00 – 0:00. If both periods of a day are set to 0:00 – 0:00, the unit will
not run at 1/1-speed that day.
Normal speed
Monday
Per 1: 07:00 – 16:00
Per.2: 00:00 - 00:00