Manual Corrigo E Ventilation, revision M
Chapter 6
Starting and stopping the unit
49
4.
The supply air fan or the control of the supply air pressure will be started after a preset
time.
5.
The extract air fan or the control of the extract air pressure will be started after a preset
time.
6.
Thereafter temperature control according to the configured control mode is started. Electric
heating, if configured, is not started until a run signal from the supply air fan or flow
switch has been received. And not yet activated pumps will be started.
7.
After a pre-set delay, the alarm handling system is activated. The unit is in normal running
mode.
6.4 Stop sequence
Stopping of the unit will run according to the following sequence:
1.
Deactivation of the alarm handling system.
2.
Electric heating, if configured, is shut down.
3.
After individually set delay times the fans are stopped.
4.
Fresh air and exhaust air dampers are shut down
5.
Actuator signals are set to 0 and the pumps are stopped.
6.
If shutdown mode is configured, it will be activated