Manual Corrigo E Ventilation, revision M
Chapter 3
Installation and wiring
19
Wiring diagram Corrigo E28-S factory configuration
(See also the picture of the position of the terminals on page 8)
1 G
50
B
2 G0
Supply voltage 24 V AC or 24 V DC,
±15%. 50/60 Hz
51 A
3
Protective
earth
52
N
4
+C
+24 V DC. Reference for digital inputs DI.
53
E
RS485 EXOline / Modbus (not in
WEB (TCP/IP) models)
10 G
DO
Reference for digital outputs DO.
57
Net+
11
DO1
Start/stop supply air fan (SAF) 1/1-speed
58
Net-
12
DO2
Start/stop extract air fan (EAF) 1/1-speed
59
Egnd
LON-connection (LON-versions only)
13
DO3
Start/stop supply air fan (SAF) 1/2-speed
14
DO4
Start/stop extract air fan (EAF) 1/2-speed
71
DI1
Filter guard, supply air and extract air
15
DO5
Start/stop Circulation pump, Heating
72
DI2
Run indication /alarm, Circ. pump Heating
16 DO6 Fire
dampers
73 DI3 Run
indication /alarm, Circ. pump Cooling
17
DO7
Sum alarm A + B
74
DI4
Fire alarm
75
DI5
Fire damper end-switch monitoring
30
Agnd
Reference pole for analogue inputs AI
76
DI6
Extended
running
1/1-speed
31
AI1
Outdoor temperature sensor
77
DI7
External alarm
32
AI2
Supply air temperature sensor
78
DI8
External stop
33
Agnd
Reference pole for analogue inputs AI
34
AI3
Extract air temperature sensor
90
Agnd
Reference pole for analogue outputs AO
35
AI4
Room temperature sensor 1
91
AO1
Y1 Actuator Heating
92
AO2
Y2
Actuator
Exchanger
40
Agnd
Reference pole for universal inputs UI
93
AO3
Y3 Actuator Cooling
41
UI1
DI Run indication / Motor protection SAF
94
AO4
Not used
42
UI2
DI Run indication / Motor protection EAF
95
AO5
Not used
43
Agnd
Reference pole for universal inputs UI
44
UI3
De-icing sensor, heat exchanger
45
UI4
Frost protection sensor
Wiring diagram Corrigo E15-S factory configuration
1 G
50
B
2 G0
Supply voltage 24 V AC or 24 V DC,
±15%. 50/60 Hz
51 A
3
Protective
earth
52
N
4
+C
+24 V DC. Reference for digital inputs DI.
53
E
RS485 EXOline / Modbus (not in
WEB (TCP/IP) models)
10 G
DO
Reference for digital outputs DO.
57
Net+
11
DO1
Start/stop supply air fan (SAF) 1/1-speed
58
Net-
12
DO2
Start/stop extract air fan (EAF) 1/1-speed
59
Egnd
LON-connection (LON-versions only)
13
DO3
Start/stop Circulation pump, Heating
14
DO4
Sum alarm A + B
71
DI1
Run indication / Motor protection SAF
72
DI2
Run indication / Motor protection EAF
30
Agnd
Reference pole for analogue inputs AI
73
DI3
Run indication /alarm, Circ. pump Heating
31
AI1
Outdoor temperature sensor
74
DI4
Extended running
32
AI2
Supply air temperature sensor
33
Agnd
Reference pole for analogue inputs AI
90
Agnd
Reference pole for analogue outputs AO
34
AI3
Frost protection sensor
91
AO1
Y1 Actuator Heating
35
AI4
Room temperature sensor 1
92
AO2
Y2 Actuator Exchanger
93
AO3
Y3 Actuator Cooling