Manual Corrigo E Ventilation, revision M
Chapter 16
Configuration
80
Fan output
when free cooling
SAF: 0 %
EAF: 0 %
Outdoor sensor
placed in intake
channel
No
For detailed description, see section 5.1.6 Free cooling.
16.11 Support control
Note: If support control without EAF (extract air fan) is selected, a recirculation damper must be
used. See more in section 5.1.5.
Support control
Active: Yes
EAF running during
support contr: Yes
Minimum running time
Min. run time for
support ctrl: 20 min
For detailed description, see section 5.1.5 Support control.
16.12 CO2/VOC Demand control
CO2/VOC active
Never
Type: Mixing dampers
Min. time: 20 min
Activation level
1/2-speed: 800 ppm
1/1-speed: 1000 ppm
diff: 160 ppm
For detailed description, see the section Demand control.
16.13 Fire function
Fire dampers are normally configured to open on fire alarm. However, via the display you can
configure them to be normally open instead.
In Corrigo controllers of generation 1, it was possible to choose whether the extract air fan should
be activated on fire alarm or if both fans should be stopped.
For generation 2 controllers, you can use E tool to configure the air handling unit’s running mode
on fire alarm. The following choices are possible: Stopped, continuous run, run via normal start/stop
conditions, only supply air fan in operation, only extract air fan in operation.
For compatibility reasons, the old function has not been removed in generation 2 controllers. This
means that old configuration files can be used in new Corrigo controllers as well. If the running
mode in the new application has been set to another value than Stopped, this value will take
precendence over the value in the old application.
There is a digital input for detection of open and closed position of the fire dampers.
All dampers must be wired to the same output in order to get correct results.