Chapter 14 Manual / Auto
General
In this menu the running mode of all the configured output signals and a number of control
functions can be manually controlled. This is a very handy feature which simplifies the checking of
individual functions in the Corrigo.
The running mode for the whole unit is set in the menu Running mode. See section 9.1.
The supply air controller's output signal can be manually set (Manual/Auto) to any value between 0
and 100%. The temperature output signals will change accordingly if they are in Auto mode. It is
also possible to manually control each of the temperature output signals individually.
All the configured digital outputs can be set to On, Off or Auto.
Since leaving any of the outputs in manual control will disrupt the normal control, an alarm will be
generated as soon as any output is set to a manual mode.
Since the menus vary according to the configuration of the outputs only the most common ones will
be shown here. For the digital signals you can normally choose between Auto and On and Off or
similar words indicating the two possible manual states of the digital output.
Manual / Auto
Supply air controller running mode. Can be set to Auto, On or Off. In manual mode the output
signal can be set 0…100%. The outputs Y1, Y2 and Y3, if in Auto-mode, will follow the signal
according to the set split values.
Supply temp contr.
Auto
Manual set: 42.0
Start signal SAF and EAF
Can be set to Auto, Manual 1/1-speed, Manual 1/2-speed and Off. Manual 1/2-speed is not valid for
single speed fans.
SAF
Auto
EAF
Auto
With pressure controlled fans you get the following menu: Can be set to Auto, Manual normal,
Manual reduced and Off. In Manual mode the output signal can be set 0…10 V.
Pressure SAF: Auto
Manual set: 0.0
EAF: Auto
Manual set: 0.0