Manual Corrigo E Ventilation, revision M
Chapter 3
Installation and wiring
22
Empty wiring diagram Corrigo E282-S
1 G
50
B
2 G0
Supply voltage 24 V AC or 24 V DC,
±15%. 50/60 Hz
51 A
3
Protective
earth
52
N
4
+C
+24 V DC. Reference for digital inputs DI.
53
E
RS485 EXOline / Modbus (Port 1)
54
B
10 G
DO
Reference for digital outputs DO.
55
A
11 DO1
56 N
12 DO2
57 E
RS485 EXOline / Modbus (Port 2)
13 DO3
14 DO4
71 DI1
15 DO5
72 DI2
16 DO6
73 DI3
17 DO7
74 DI4
75
DI5
30
Agnd
Reference pole for analogue inputs AI
76
DI6
31 AI1
77 DI7
32 AI2
78 DI8
33
Agnd
Reference pole for analogue inputs AI
34
AI3
90
Agnd
Reference pole for analogue outputs AO
35 AI4
91 AO1
92
AO2
40
Agnd
Reference pole for universal inputs UI
93
AO3
41 UI1
94 AO4
42 UI2
95 AO5
43
Agnd
Reference pole for universal inputs UI
44 UI3
45 UI4
Empty wiring diagram Corrigo E152-S
1 G
50
B
2 G0
Supply voltage 24 V AC or 24 V DC,
±15%. 50/60 Hz
51 A
3
Protective
earth
52
N
4
+C
+24 V DC. Reference for digital inputs DI.
53
E
RS485 EXOline / Modbus (Port 1)
54
B
10 G
DO
Reference for digital outputs DO.
55
A
11 DO1
56 N
12 DO2
57 E
RS485 EXOline / Modbus (Port 2)
13 DO3
14 DO4
71 DI1
72
DI2
30
Agnd
Reference pole for analogue inputs AI
73
DI3
31 AI1
74 DI4
32 AI2
33
Agnd
Reference pole for analogue inputs AI
90
Agnd
Reference pole for analogue outputs AO
34 AI3
91 AO1
35 AI4
92 AO2
93
AO3
Содержание Corrigo E series