64 | City Series CB60E-1
installation
Vent Guard - if required*
(Part #946-
604
/P)
5" (127 mm)
8" (203 mm)
Notes:
1. Liner sections should be continuous without any joints
or seams.
2. Only Flex pipe purchased from Regency
®
may be used
for Flex installations
3. Horizontal vent must be supported every 3 feet.
4. Regency
®
Direct Vent System (Flex) is only approved
for horizontal terminations.
5. Flex system can only be used up to a maximum
continuous vent length of up to 10 feet. If longer runs
are required, rigid pipe must be used.
Horizontal Terminations -
Flex Vent 5" x 8
"
These venting systems, in combination with the CB60E-1 Direct Vent Gas Fireplace, has been tested and listed as a direct vent heater system by Intertek. The
location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in "Exterior Vent Termination Locations" section.
Regency
®
Direct Vent (Flex) System Termination Kits include all the parts needed to install the CB60E-1 using a flexible vent.
FPI Kit # Length Contains:
#946-615
4 Feet
1) 8” flexible liner (Kit length)
2) 5” flexible liner (Kit length)
3) spring spacers
4) thimble
5) AstroCap XL termination cap
6) screws
7) tube of Mill Pac
8) plated screws
9) S.S. screws #8 x 1-1/2” drill point
10) vinyl siding standoff
#946-618
6 Feet
#946-616
10 Feet
*Unit is not exactly as shown.
Содержание City 686-927
Страница 55: ...City Series CB60E 1 55 installation 2 x 4 shown Max 2 x 6 Typical Installations Flush Install Recessed Install ...
Страница 115: ...City Series CB60E 1 115 notes ...
Страница 120: ...120 City Series CB60E 1 warranty ...
Страница 121: ...City Series CB60E 1 121 notes ...
Страница 122: ...122 City Series CB60E 1 notes ...
Страница 123: ......