City Series CB60E-1 | 79
installation
Gas Pipe Pressure Testing
The appliance must be isolated from the gas sup-
ply piping system by closing its individual manual
shut-off valve during any pressure testing of the
gas supply piping system at test pressures equal
to or less than 1/2 psig. (3.45 kPa). Disconnect
piping from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure,
both inlet and manifold pressures
should be checked using the valve
pressure ports on the valve.
1 Make sure the unit is in the "OFF" position.
2. Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a 1/8" wide flat
screwdriver.
3. Attach manometer to "IN" and/or "OUT" pres-
sure tap(s) using a 5/16" ID hose.
4. Turn the unit on with the remote or wall switch
5. The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified on the safety label.
6. When finished reading manometer, turn off
the unit, disconnect the hose and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Note: Screw should be snug, but do
not over tighten.
High Elevation
This unit is approved for altitude 0 to 4500 ft.
(CAN1 2.17-M91).
Gas Line Installation
Since some municipalities have additional local
codes it is always best to consult with your local
authorities and the CAN/CGA B149 installation code.
For USA installations follow local codes and/or
the current National Fuel Gas Code, ANSI Z223.1.
When using copper or flex connectors use only
approved fittings. Always provide a union so that
gas lines can be easily disconnected for servicing.
Flare nuts for copper lines and flex connectors are
usually considered to meet this requirement.
NOTE: A shutoff / dante valve should be
supplied in or near the unit (or as per local
codes) for ease of servicing this appliance.
IMPORTANT: Always check for gas leaks with
a soap and water solution or gas leak detec
-
tor. Do not use open flame for leak testing.
CB60E-1
NG SYSTEM DATA
Max. Supply
Pressure
14"WC (3.45 kPa)
Min. Supply
Pressure
5" WC (1.25 kPa)
Manifold Pressure
3.8" WC (0.87 kPa)
Orifice Size
#32 DMS
Maximum Input
39,000 Btu/h
(11.43 kW)
Minimum Input
21,000 Btu/h
(6.15 kW)
CB60E-1
LP SYSTEM DATA
Max. Supply Pressure 14"WC (3.45 kPa)
Min. Supply Pressure
11" WC (2.73 kPa)
Manifold Pressure
10.5" WC (2.49 kPa)
Orifice Size
#50 DMS
Maximum Input
36,000 Btu/h
(10.55 kW)
Minimum Input
19,500 Btu/h
(5.71 KW)
Note: If you have an incorrect flame pattern,
contact your Regency
®
dealer for
further instructions.
Incorrect flame pattern will have small, probably
yellow flames, not coming into proper contact with
the rear burner or flame sensor.
Pilot Adjustment
Periodically check the pilot flames. Correct flame
pattern has two strong blue flames: 1 flowing around
the flame sensor and 1 flowing across the burner (it
does not have to be touching the burner).
885 S.I.T. Valve Description
1) 6 Stage flame adjustment
2) Pilot adjustment
3) Outlet Pressure Tap
4) Inlet Pressure Tap
5) Pilot Outlet
6) Main Gas Outlet
7) Main Gas Inlet
1
2
3
4
6
5
7
Содержание City 686-927
Страница 55: ...City Series CB60E 1 55 installation 2 x 4 shown Max 2 x 6 Typical Installations Flush Install Recessed Install ...
Страница 115: ...City Series CB60E 1 115 notes ...
Страница 120: ...120 City Series CB60E 1 warranty ...
Страница 121: ...City Series CB60E 1 121 notes ...
Страница 122: ...122 City Series CB60E 1 notes ...
Страница 123: ......