3
G
ENERAL
M
ETER
S
PECIFICATIONS
1.
DISPLAY:
6 digit, 0.56" (14.2 mm) red sunlight readable or standard green
LED
2.
POWER:
AC Versions:
AC Power: 85 to 250 VAC, 50/60 Hz, 18 VA
Isolation: 2300 Vrms for 1 min. to all inputs and outputs. (300 V working)
DC Versions:
DC Power: 11 to 36 VDC, 14 W
(derate operating temperature to 40° C if operating <15 VDC and three
plug-in option cards are installed)
AC Power: 24 VAC, ± 10%, 50/60 Hz, 15 VA
Isolation: 500 Vrms for 1 min. to all inputs and outputs (50 V working).
3.
SENSOR POWER:
12 VDC, ±10%, 100 mA max. Short circuit protected
4.
KEYPAD:
3 programmable function keys, 5 keys total
5.
USER INPUTS:
Three programmable user inputs
Max. Continuous Input: 30 VDC
Isolation To Sensor Input Commons: Not isolated
Logic State: Jumper selectable for sink/source logic
Response Time: 6 msec. typical; function dependent. Certain resets, stores
and inhibits respond within 25 µsec if an edge occurs with the associated
counter or within 6 msec if no count edge occurs with the associated
counter. These functions include
!"#$"%
,
!"#$"&
,
'%#$"%
,
'%#$"&
,
()'(*"
,
$"+#&
, and
,#)#$"
. Once activated, all functions are latched for
50 msec min. to 100 msec max. After that period, another edge/level may
be recognized.
6.
MEMORY:
Nonvolatile E
2
PROM retains all programmable parameters and
display values.
7.
CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Recognized Component, File #E179259, UL3101-1, CSA C22.2 No.
1010-1
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
UL Listed, File #E137808, UL508, CSA C22.2 No. 14-M95
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate #UL/5854B/UL
CB Scheme Test Report #02ME04503-04122002
Issued by Underwriters Laboratories, Inc.
IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
IP20 Enclosure rating (Rear of unit), IEC 529
ELECTROMAGNETIC COMPATIBILITY
Note:
Refer to EMC Installation Guidelines section of the bulletin for additional
information.
8.
ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50°C (0 to 45°C with all three plug-in
cards installed)
Storage Temperature Range: -40 to 60°C
Operating and Storage Humidity: 0 to 85% max. relative humidity non-
condensing
Altitude: Up to 2000 meters
9.
CONNECTIONS:
High compression cage-clamp terminal block
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-14 AWG copper wire
Torque: 4.5 inch-lbs (0.51 N-m) max.
10.
CONSTRUCTION
: This unit is rated for NEMA 4X/IP65 outdoor use.
IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece
bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and
mounting clip included.
11.
WEIGHT:
10.1 oz. (286 g)
V
IN
> 3.6 VDC
V
IN
< 0.9 VDC
Inactive
V
IN
< 0.9 VDC
V
IN
> 3.6 VDC
Active
SINKING INPUTS
5.1 K
Ω
Ω
pull-up to +12 V
SOURCING INPUTS
5.1 K
Ω
Ω
pull-down
INPUT STATE
Power mains class A
Enclosure class A
EN 55011
RF interference
Emissions to EN 50081-2
150 KHz - 80 MHz
Level 3; 10 V/rms
EN 61000-4-6
RF conducted interference
Level 3; 2 Kv power
Level 4; 2 Kv I/O
EN 61000-4-4
Fast transients (burst)
80 MHz - 1 GHz
Level 3; 10 V/m
EN 61000-4-3
Electromagnetic RF fields
Level 3; 8 Kv air
Level 2; 4 Kv contact
EN 61000-4-2
Electrostatic discharge
200 Hz, 50% duty cycle
900 MHz
±
5 MHz
Immunity to EN 50082-2
Level 3; 10 V/m
ENV 50204
Simulation of cordless telephones