SPECIFICATIONS (Cont’d)
7.
OUTPUTS
:
Solid-State
: Current sinking NPN open collector transistors.
I
SNK
= 100 mA max., V
OH
= 30 VDC max., V
OL
= 1 V @ 100 mA.
Programmable Timed Output
: The timed output can be programmed from
0.01 sec. to 99.99 sec., ±0.1% + 10 msec. max. The timed output is set for
0.10 second at the factory.
8.
MEMORY RETENTION
:
Non-volatile E
2
PROM retains all programmed information when power is
removed or interrupted.
Power Cycles(ON/OFF):
100,000 min.
Data Retention:
10 years min.
9.
INPUT, POWER, AND OUTPUT CONNECTIONS
:
Fixed terminal block.
10.
ENVIRONMENTAL CONDITIONS
:
Operating Temperature
: 0 to 50°C
Storage Temperature
: -40 to 70°C
Operating and Storage Humidity
: 85% max. (non-condensing) from 0°C
to 50°C.
Altitude
: Up to 2000 meters
11.
CERTIFICATIONS AND COMPLIANCES
:
SAFETY
IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
Type 4X Enclosure rating (Face only), UL50
ELECTROMAGNETIC COMPATIBILITY
:
Notes:
1. Power lines had an external EMI filter, (RLC #LFIL0000 or equivalent)
installed.
Refer to the EMC Installation Guidelines section of this bulletin for
additional information.
12.
CONSTRUCTION
: High impact plastic case with clear viewing window.
Front panel meets NEMA 4X/IP65 requirements for indoor use, when
properly installed. (Panel gasket, mounting clip, nut fasteners, and screws
included with unit.) Installation Category II, Pollution Degree 2.
13.
WEIGHT
: 0.2 lbs (91 g).
SWITCH SET-UP
S1 - DIS.RST.:
Disables front panel reset.
EN. RST.:
Enables front panel reset.
S2 to S5:
These are the mode select DIP switches.
See Modes of Operation for the switch settings of a specific mode.
S6 - 0.00:
Sets the timer to display two decimal places.
0.000:
Sets the timer to display three decimal places.
S7 - Sec.:
Sets the timer to display in seconds.
Min.:
Sets the timer to display in minutes.
MODES OF OPERATION FOR DUAL PRESET LNXNT TIMER
MODE 0 LATCHED OUTPUTS AT PRESET, MANUAL RESET TO
ZERO
The unit times from zero, when preset 1 is reached,
output 1 turns on and time continues to accumulate.
When preset 2 is reached, output 2 turns on and time
continues to accumulate. When a manual reset is performed, the time
resets to zero, the outputs turn off, and the cycle starts again.
MODES OF OPERATION, DIP SWITCH SET-UP
The DIP switches for the various operating modes are accessible from the rear of the unit.
Notes
1. A manual reset, either from the front panel reset (if enabled) or remote reset overrides any condition or state of the timer and
begins the cycle again.
2. In modes four, five, twelve, and thirteen, the output may appear to be latched if the time delay is longer than the time required
for the timer to reach the preset point or zero.
BLOCK DIAGRAM
2
Enclosure class A
EN 55011
RF interference
Emissions to EN 50081-2
Power mains class A
150 KHz - 80 MHz
Level 3; 10 V/rms
1
EN 61000-4-6
RF conducted interference
Level 3; 2 Kv power
1
Level 4; 2 Kv I/O
EN 61000-4-4
Fast transients (burst)
80 MHz - 1 GHz
Level 3; 10 V/m
EN 61000-4-3
Electromagnetic RF fields
Immunity to EN 50082-2
Electrostatic discharge
EN 61000-4-2 Level 2; 4 Kv contact
Level 3; 8 Kv air