20
PARAMETER MENU
!
"
3
/%/.#!
COUNTER C SCALE MULTIPLIER
The number of input counts is multiplied by the scale multiplier and the scale
factor to obtain the desired process value. A scale multiplier of 1 will result in
only the scale factor affecting the display. (Details on scaling calculations are
explained at the end of Module 1 section.)
!
"
*+*1
/ /*'
COUNTER C OPERATING MODE *
!
"
722
//*'#$
COUNTER C COUNT LOAD VALUE
When reset to count load action is selected, Counter C will reset to this value.
!
"
*+
/ &89&
COUNTER C RESET POWER-UP *
Counter C may be programmed to reset at each meter power-up.
!
"
01!+
/!1%1'
COUNTER C RESET ACTION
When Counter C is reset, it returns to zero or Counter C count load value.
This reset action affects all Counter C resets, except the Setpoint Counter Auto
Reset Action in Module 6.
!
"
2
/$1/&'
COUNTER C DECIMAL POSITION
This selects the decimal point position for Counter C and any setpoint value
assigned to Counter C. The selection will also affect Counter C scale factor
calculations.
!
"
3422222
/%/5./
COUNTER C SCALE FACTOR
The number of input counts is multiplied by the scale factor and the scale
multiplier to obtain the desired process value. A scale factor of 1.00000 will
result in the display of the actual number of input counts. For
.
(Numeric
transmissions) modes of operation, the input signal is scaled directly. For
.$$
.<
and
%E< .<
modes of operation, the math is performed on the input signals
and then the result is scaled. To achieve correct results, both Input A and Input
B must provide the same amount of pulses per unit of measurement. (Details on
scaling calculations are explained at the end of Module 1 section.)
2422223
to
6466666
866666
to
666666
;1%
*+
3
243
2423
01!+
/*'#$
Module 5 is the programming for Counter C. For maximum input frequency,
the counter operating mode should be set to
*+*1
when not in use. When set to
*+*1
the remaining related parameters are not accessible. The C annunciator
indicates that Counter C is being shown in the Display Mode. An Exchange
Parameter List feature for scale factor and count load values is explained in
Module 2.
2
2422
242222
242
24222
2422222
%#.:1
%E< .<
.$$ .<
.
*+*1
Select the operating mode for Counter C.
*
Factory Setting can be used without affecting basic start-up.
6.5 MODULE 5 - C
OUNTER
C I
NPUT
P
ARAMETERS
(
80!"#!
)
See Serial Communications for details.
SLAVE
Note: When using Add Ab or Sub Ab, Counter A, B and C must all be reset
at the same time for the math to be performed on the display values.
Counter C counts the incoming pulses from Counter A and B
inputs as per Counter A and B modes of operation and
subtracts the B counts from the A counts. The result is scaled
only according to Counter C parameters. (Example: If
Counter A is set for Count X1 mode and Counter B is set for
Count X2 mode, then Counter C will increment by 1 for each
pulse received on Input A and decrement by 2 for each pulse
received on Input B less any effects of scaling.)
Sub Ab
Counter C counts the incoming pulses from Counter A and B
inputs as per Counter A and B modes of operation. The
result is scaled only according to Counter C parameters.
(Example: If Counter A is set for Count X1 mode and Counter
B is set for Count X2 mode, then Counter C will increment by
1 for each pulse received on Input A and increment by 2 for
each pulse received on Input B less any effects of scaling.)
Add Ab
Counter C counts the incoming pulses from Counter A input
as per Counter A mode of operation. The signal is scaled
only according to Counter C parameters.
A
Does not count.
NONE
(PAXI only)
PAXC & I
Содержание CUB 1
Страница 30: ...7 This page intentionally left blank...
Страница 46: ...5...
Страница 47: ...6...
Страница 48: ...7...