Retractable Flap Barrier Operation Manual
16
- -
7.
Debugging Introduce
Once the mechanical and electrical installation of the turnstile has been completed,
it can be put into service.
1.
Checking the wiring connection
Please carefully check all wiring are correctly connected according to diagram,
check connectors are not loose; check if the equipment is well grounded. If
everything is ok, then you can test the devices after power on.
please make sure the equipments are reliable grounded, unless you can’t do
debugging.
2.
Function debugging
1.
External entry opening signal and exit opening signal;
2.
Without valid access controller signal, acoustic signal for announcement of
unauthorised use. (extended voice prompt modular available).
3.
Equipment Operation after power on
Normally Closed model: turnstile arm will up automatically after power on, it will
drop automatically when power failure.
Normally Open model: barrier will open automatically after power on, and keep
normally open status.
---------------------------------------------------------------------------------------------------
Precautions:
(1)
Please do not use the system when there is lightning, otherwise the
turnstile may be damaged.
(2)
It is required to connect reliably the protection grounding of the system to