Retractable Flap Barrier Operation Manual
24
- -
4, NP02 recovery parameters (both main and sub-boards are required)
5, through the actual situation setting NP07 set the motor's forward and reverse
(main and auxiliary boards are required)
6, automatic shutdown of power failure
3
.
the power (E-SL) voice report communication failure
Solution:
1.
Check if the communication line connection is correct, TA to TA TB to TB.
2.
Check whether the board is a master or a pair. The main board corresponding to
the label "Z" is corresponding to the label "F". You can also change the NP09.
Value to change the main and sub mode of the board (0 is dominant, 1 is
secondary)
4. After the power is turned on, the zero position of the gate is not allowed.
Solution:
1. The iron piece and the Retractable Flap arm of the mounting magnet are locked
at about 90 degrees (the magnet has a polarity). The parameter DP03 is adjusted
according to the voice.
Set the zero position.
5. The limit indicator does not light.
Solution:
1. The sensor of this system is Hall induction (induction magnet). The magnet is
divided into north and south poles (N/S), and the polarity of the magnet is
changed.
Sixth, the Retractable Flap arm can not open 90 degrees.
Solution: