RADWIN 5000 SCB Jet User Manual
Release 4.2
5-6
Log on to the HBS via a Server (Optional)
RADWIN Manager Setup
Figure 5-7: Log on window showing SNMP settings.
You may choose the SNMP version. If your firewall blocks SNMPv3 messages for security
reasons, them use SNMPv1.
If you are using Trap Authentication, enter the User and Password. Leaving these fields blank
or incorrect, will not prevent you from logging on. You will not be able to see trap messages
directed to the trap message address associated with a defined user. The allocation and
association of a trap address with a user is described for PtP in
Chapter 9, Trap Destinations
and for PtMP in
Chapter 14, Trap Destinations
.
The following table summarizes these options:
The Network Manager should change the default passwords as soon as possible, particularly
if SNMPv3 is to be used.
Table 5-2: User types, default passwords and function
User Type
Default
Password
Function
SNMPv1
SNMPv3
Community
Community
String
Password
Default
Value
Observer
admin
Monitoring
Read-Only
public
Read-Only public
Operator
admin
Installation,
configuration
Read-Write
netman
Read-
Write
netman
Installer
wireless
Operator plus
set-band
Read-Write
netman
Read-
Write
netman