26
INTAC
®
MENU
DISPLAY
OPTIONS
MFG
DEFAULT
DESCRIPTION
714
Burner 3 Set Point
RANGE: 5 to 100%
75%
% power at which burner #3 turns on
(Factory option only)
715
Burner 3 Hys
RANGE: 1 to 99%
3%
% power below Burner #3 set point at which burner #2 turns
off
(Factory option only)
716
Post Purge Time
RANGE: 5 to 999 seconds
30 seconds
Time the combustion fans will run after the burners turn off
(Factory option only)
717
VFD Intensity
RANGE: 1 to 8
4
Adjusts the intensity of the display panel
(Factory option only)
718
Range Checking
Off
Input error checking is off
(Factory option only)
On
x
Input error checking is on
719
RANGE: 0
-
15 seconds
5
Time after a low water state is sensed that the heater output
will be maintained
(Factory option only)