Error Code Summary
E01
Safety Circuit Open
An open circuit exists in the Safety Circuit. Check the following:
Terminals J6
-
5 & J6
-
6 High Limit Humidistat
Terminals J6
-
4 & J6
-
3 Air Flow Switch
Terminals J6
-
2 & J6
-
1 Over
-
Temp Switch*
Continuity MUST exist across these terminals to clear alarm
* SX and SXDDR models
do not
have an Over
-
Temp Switch
E02
Dedicated Event Circuit Open
An open circuit exists in the Dedicated Event Circuit. Check the following:
Terminals J1
-
5 & J1
-
6 Dedicated Event
Continuity MUST exist across these terminals to clear alarm
(Configuration Menu 520 turns this feature ON or OFF)
E03
Control RH Under Range
CHECK FOR THE FOLLOWING CONDITIONS:
1) Lost input signal from primary humidistat or Building Management System
2) Input signal below 6% RH (below 4 mA DC)
3) Input signal between 100% and 105%
Verify that Menus 502, 504, 505, & 506 match the type of input. Check
signal at the input terminals:
Terminal J2
-
1 = Voltage (+) Input
Terminal J2
-
3 = Voltage (
-
) / Current (
-
) Input
Terminal J2
-
2 = Current (+) Input
E03
Control RH Over Range
CHECK FOR THE FOLLOWING CONDITIONS:
1) Input signal between 100% and 105% (process control circuits only)
Verify that Menus 502, 504, 505, & 506 match the type of input. Check
signal at the input terminals:
Terminal J2
-
1 = Voltage (+) Input
Terminal J2
-
3 = Voltage (
-
) / Current (
-
) Input
Terminal J2
-
2 = Current (+) Input
E03
Control RH AD Underflow
-
AD Overflow
Check for REVERSE polarity or EXCESSIVE SIGNAL on the input terminals:
Terminal J2
-
1 = Voltage (+) Input
Terminal J2
-
3 = Voltage (
-
) / Current (
-
) Input
Terminal J2
-
2 = Current (+) Input
E03
Control RH Calibration
Input not calibrated properly