21
INTAC
®
MENU
DISPLAY
OPTIONS
MFG
DEFAULT
DESCRIPTION
101
RH Set Pt
RANGE: 0% to 100% RH
45%
Space or return air humidification setpoint
102
HL RH Set Pt
RANGE: 0% to 100% RH
80%
Supply air high
-
limit setpoint
103
RH Lo Alarm
RANGE:
-
100% to
-
1% RH
-
5%
Low humidity alarm activates when actual RH is below setpoint
104
RH Hi Alarm
RANGE: 1% to 100% RH
5%
High humidity alarm activates when actual RH is above setpoint
201
Operation Mode
Normal
x
Normal operation mode
Stand
-
by
Output of humidifier shut off while in Stand
-
by mode
Forced Drain
Drain valve output energized, humidifier output shut off
Flush
Fill valve and drain valve outputs are energized, humidifier output shut
off
202
Drain Duration
RANGE: 0 to 120 minutes
Varies
Time drain valve is energized (in minutes) during Auto
-
drain cycle
203
Drain Interval
RANGE: 1 to 500 Hours
40
Time between Auto
-
drain cycles in hours of operation
204
Cool Down Delay
RANGE: 0 to 150 Seconds
150
The fill valve is energized for this time period to allow colder makeup
water to cool the tank before the Auto
-
drain cycle begins.
205
Cool Down Temp
RANGE: 80° to 212°F
140
The tank water temperature must be below this value before the drain
valve is energized during an Auto
-
drain cycle. The fill valve is ener-
gized to allow colder makeup water to cool the tank. Used in place of
cool down delay when an optional tank thermocouple is installed
RANGE: 27° to 100° C
60
Same description as above except for Celsius units are used
206
Fill Delay
RANGE: 0 to 15 Seconds
5
Water overfill time delay to help flush surface minerals down the tank
overflow on each refill cycle
207
H2O Set Pt
RANGE: 40° to 200° F
40
If there is no call for humidification the heating source will be turned
on to maintain this temperature. This can be used for freeze protection
(40°) or stand
-
by water temperature (160°)
RANGE: 4° to 93°C
4
Same description as above except for Celsius units are used
208
Water Hysteresis
RANGE: 1° to 50°F
3
Accuracy of water temperature control or deadband
RANGE: 1° to 28°C
2
Same description as above except for Celsius units are used
209
End of Use Drain
RANGE: 0 to 168 Hours
48
When there is no call for humidification for this many consecutive
hours the tank will drain completely.
210
Time to Clean
RANGE: 0 to 365 Days
30
Used to set a reminder to clean the tank after an adjustable time peri-
od of run time. The humidifier will continue to operate even after the
“Time to Clean the Tank” message is displayed.
211
Clean Reset
Off
x
Time to clean timer is accumulating run time
On
Select “On” to reset the accumulated run time
INTAC
®
Configuration Codes Complete Listing