24
519
Out Process Hi
RANGE: 10.00 to 20.00 mA
20.00
Process output signal—High range in Milliamps
RANGE: 3.00 to 10.00
VDC
10.00
Process output signal—High range in Volts
520
Dedicated Input
Not Used
x
Dedicated input turned off
Dedicated Event
INTAC
®
terminals J1
-
5, J1
-
6
OPEN
; humidifier output shuts off
Hi Limit Open
Used to display when supply air humidity is above the safety
high limit setpoint. Connect high limit to terminals J1
-
5, J1
-
6
Auto Drain
Closed contact will start an auto drain
Pnl Lockout
INTAC
®
terminals J1
-
5, J1
-
6
CLOSED
; all menus LOCKED
including menu 520
521
Temp Units
Fahrenheit
x
All temperatures in all screens and menus are in °F
Celsius
All temperatures in all screens and menus are in °C
522
Capacity Units
Lbs/Hr
x
All capacities in all screens and menus are in lbs/hr
Kgs/Hr
All capacities in all screens and menus are in kgs/hr
523
Unit Capacity
RANGE: 2 to 9999
Varies
Unit capacity in lbs/hr
RANGE: 2 to 9999
Varies
Unit capacity in kgs/hr
525
Menu Access
All Menus
x
No menus are blocked from changing configurations
100 & 200 Menus
All menus VIEW ONLY except menus 100, 200, and 500
100 Menu
All menus VIEW ONLY except menus 100 and 500
No Menus
All menus VIEW ONLY except menu 500
701
Control Type
SCR
Varies
Solid state relay output offers the best modulating control
Steam
Modulating VDC or mA DC output signal to operate valve
actuator
Gas
For use with up to 3 gas burners
702
Active Heaters
1
Varies
One active heater
(Factory option only)
2
Two active heaters
3
Three active heaters
4
Four active heaters
INTAC
®
MENU
DISPLAY
OPTIONS
MFG
DEFAULT
DESCRIPTION